AC Output Modules
FEATURES
• Transient Protection: Meets the
requirements of IEEE 472, “Surge
Withstanding Capability Test”
• SPST, Normally Open
• Zero Crossing Turn-On
• UL, CSA, CE, TÜV Certified
• Optical Isolation
• OpenLine® and G5 Modules
Provide Replaceable 5x20 mm
Glass Fuses
• Built-in Status LED
• Lifetime Warranty
70L-OAC
70G-OAC
70-OAC
70M-OAC
4
3
2
1
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
thejunctiontemperaturesto100°C.Information
is based on steady state heat transfer in a 2
cubic foot sealed enclosure.
DIMENSIONS
STANDARD, G5 PACKAGES
MINIATURE PACKAGE
Forcompletedimensionaldrawings,seepages
L-4 or L-5.
OPENLINE PACKAGE/CH
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent. OpenLine® fuses are
3.15 Amp Littelfuse part number 2173.15.
-40˚
-20˚
0
20˚
40˚
60˚
80˚
100˚
AMBIENT TEMPERATURE (˚C)
Figure 1
CIRCUITRY
Standard, Mini, G5
OpenLine®
TYPICAL WIRING FOR MODULE 0
1
I/O MODULE
PIN #
LOAD
LOAD
GND
Vcc
VAC
5
6
SNUBBER
CHANNEL A
LOAD
1
1
2
A
OPTICAL
SNUBBER
ISOLATION
TRIGGER
CIRCUIT
7
2
3
2
3
CH. A CONTROL
B
OPTICAL
SNUBBER
ISOLATION
Rx
CH. B CONTROL
MODULE ID
LOAD
4
4
3
4
+
CHANNEL B
DC CONTROL
–
2.15K
TERMINAL
BLOCK #
RACK
OR
BASE
MODULE
Fuse and status LED in G5 and OpenLine modules only.
SPECIFICATIONS:ByPackageStyle
Package Style
Std (70-)
Mini (70M-)
G5 (70G-)
OL (70L-)
Specifications
Units
Load Current Range1
Maximum 1 Cycle Surge2
Maximum Turn-On-Time (60 Hz)3
Maximum Turn-Off Time (60 Hz)
Static dv/dt7
A rms
A rms
mSec
mSec
V/µsec
W/A
0.03 to 3.5
80
0.03 to 3.0
80
0.03 to 3.5
80
0.03 to 2.0/CH
30
8.33
8.33
8.33
8.33
8.33
8.33
8.33
8.33
3000
3000
3000
1.0
3000
Typ. Power Dissipation
1.0
1.0
1.0
Isolation Voltage4
V rms
4000
4000
4000
2500
Vibration5
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
IEC68-2-6
IEC68-2-27
-40 to 100
-40 to 85
Lifetime
Mechanical Shock6
Storage Temp. Range
Operating Temp. Range
Warranty
°C
°C
1
2
See Figure 1 for derating.
Maximum 10 cycle surge is 50% of 1 cycle surge. Application of maximum surge may not be repeated until module temperature has returned
to its steady state value.
3
4
5
6
7
Except 70-OAC5A5 which is 200 µSec and 70-OAC5A-11, 70M-OAC5A-11, and 70G-OAC5A-11 which are 100 µSec.
Field to logic and channel-to-channel if Grayhill racks are used.
MIL-STD-202, Method 204, 20 , 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz.
MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g.
Except part numbers with -L suffix which have a dv/dt rating of 200 V/µSec.
I/O
6
Grayhill, Inc.
• 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com