MODEL: 6BTS
3: PG 13.5
Field-mounted Two-wire
Signal Conditioners 6B-UNIT
[3] ENCLOSURE MATERIAL
A: Diecast aluminum
THERMOCOUPLE TRANSMITTER
(linearization)
S: Stainless steel casting
Functions & Features
• Accepts direct input from a thermocouple and providing a
standard 4 – 20 mA DC signal
• Linearization
[4] MOUNTING BRACKET
0: Without
1: With
• Burnout protection
• Cold junction compensation
• Rugged outdoor enclosure: stainless steel selectable
[5] OPTIONS
Burnout
blank: Upscale burnout
/BL: Downscale burnout
PACKAGE INCLUDES...
• Mounting screws
Bolt (M8 x 15): 4
Spring washer for M8: 4
Material: Stainless steel 304
• Mounting bracket assembly (option):
Mounting bracket: 1
M10 U-bolt: 2
MODEL: 6BTS–0[1][2][3][4][5]
Nut for M10: 4
Spring washer for M10: 4
Material: Stainless steel 304
Applicable pipe: 1 1/2” min.; 2” max.
ORDERING INFORMATION
• Code number: 6BTS-0[1][2][3][4][5]
Specify a code from below for each of [1] through [5].
(e.g. 6BTS-020A1/BL)
GENERAL SPECIFICATIONS
Degree of protection: NEMA 4X, IP66/IP67
Wiring conduit: See ‘Ordering information.’
Electrical connection: M3 screw terminals
(torque 0.6 N·m)
• Temperature range (e.g. 0 – 800°C)
SAFETY APPROVAL
0: None
Materials
• Transmitter housing: Diecast aluminum
Screw terminals: Nickel-plated steel
• Enclosure: Diecast aluminum or stainless steel casting
(equivalent to type 316); silver color, epoxy resin coated
Isolation: Input to output to outdoor enclosure
Output limit: Approx. 120 %
[1] INPUT THERMOCOUPLE
1: (PR) (Usable range 0 to 1760°C, 32 to 3200°F)
2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)
3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)
4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)
5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)
6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)
7: R (Usable range -50 to +1760°C, -58 to +3200°F)
8: S (Usable range -50 to +1760°C, -58 to +3200°F)
0: Specify
Zero adjustment: Approx. -0.5 – +5 % (behind the access
cover)
Span adjustment: Approx. 95 to 105 % (behind the access
cover)
Linearization: Standard
Cold junction compensation: CJC sensor attached to the
input terminals
[2] WIRING CONDUIT
0: G 1/2
1: 1/2 NPT
2: M20 × 1.5
6BTS SPECIFICATIONS
ES-8862 Rev.4 Page 1/4
http://www.m-system.co.jp/