MODEL: 60S
Field Network Modules 60-UNIT Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
ANALOG I/O MODULE
(Multiplex Transmission System)
/C02: Polyurethane coating
/C03: Rubber coating
Functions & Features
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with Multiplex Transmission System
• Saving power and I/O wiring inside an instrumentation
panel
RELATED PRODUCTS
•Special cable (model: MCN34)
72
(2.83)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
80 (3.15)
SIN-NET, RUN contact output: Euro type connector
terminal (applicable wire size: 0.2 to 2.5 mm
2, stripped
length 7 mm)
153 (6.02)
mm (inch)
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to SIN-NET to RUN contact output to power to
FG1
MODEL: 60S-16[1]-[2][3]
Power indicator: Red LED turns ON in normal conditions;
OFF when the voltage level becomes low.
RUN indicator: Red LED turns ON when the selfdiagnosis
proves normal, OFF in an abnormality.
■ RUN Contact Output: Contact opens at error
Rated load: 30 V DC @ 0.4 A (resistive load)
Maximum switching voltage: 125 V DC
Maximum switching power: 60 W
ORDERING INFORMATION
• Code number: 60S-16[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. 60S-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Minimum load: 10 mV DC @ 1 mA
NO. OF CHANNELS
Mechanical life: 5 x 10
7
cycles
16: 16 points
Self-diagnosis
Communication: The receiver modules detect loss of
communication and wire break.
CPU: Watch-dog timer
[1] I/O TYPE
1: Input
2: Output
Memory: Sum check
Power voltage: Detects when the voltage supply to the
CPU drops.
[2] POWER INPUT
AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
60S SPECIFICATIONS
ES-6612 Rev.3 Page 1/5
http://www.m-system.co.jp/