Power Entry Modules with Line Filter
www.schurter.com/PG06
Felcom 54
IEC Appliance Inlet C14 Modular Assembling Options
Standard- or Medical-Filter
Snap-In Version
5411.XX5X.XXX
Appliance inlet
Fuseholder
5431.X05X.XXX
Appliance inlet
Appliance outlet
Switch
Line filter
Line filter
C14
F
70° C
70° C
Description
- Panel Mount:
Characteristics
- Modular component selection
- Individual components soldered on a printed circuit board
- Plug removal necessary for fuse-link replacement
Snap-in version from front side
- 2 - 5 Functions:
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- Technical data of filter-components see blockfilter type 5500
- Fully insulated from the rear
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Appliance Inlet Protection class I, Connector, Line Switch 2-pole, Fu-
seholder for fuse-links 5 x 20 mm 1 or 2 pole, Line filter in standard
and medical version
- Solder terminals 3.5 x 0.8 mm or quick connect terminals 6.3 x 0.8
mm
Approvals
- VDE Certificate Number: 101307
- UL File Number: E72928
Other versions on request
- Line switch with other rocker marking
References
Alternative: version without line filter Felcom 64
Alternative: Standard version
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, Mating Connectors,
e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-
Drawings, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Solder terminals 3.5 x 0.8 mm or quick
connect terminals 6.3 x 0.8 mm
Snap-in: 1/1.2/1.5/2/2.5/3 mm1/1.2/1.
5/2/2.5/3 mm
Appliance-Inlet/-Outlet
Fuseholder
C14 acc. to IEC 60320,
F acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C,
10 A, Protection Class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical Details
Standard Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Terminal
Line Switch
Line Filter
MTBF
Panel Thickness s
Material: Housing
Thermoplastic, black, UL 94V-0
> 1'400'000 h acc. to MIL-HB-217 F
1
Connectors