DIESEL GENERATOR SET
2000-XC6DT2
/
/
2000 kWe 60 Hz Standby
380 - 13.8kV
(Reference 1800-XC6DT2 for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
Voltage (L-L) 380V
480V**
3
600V
3
4160V
3
12470V
3
13200V
3
13800V
3
Phase
3
PF
0.8
0.8
0.8
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
60
60
kW
kVA
Amps
2000
2500
3803
2000
2500
3007
2000
2500
2406
2000
2500
347
2000
2500
116
2000
2500
109
2000
2500
105
skVA@30%
Voltage Dip
Generator
Model*
Temp Rise
Connection
4300
5800
3600
5100
C/F
C/F
C/F
744RSL4176
130 °C/40 °C 130 °C/40 °C
4 BAR WYE 4 BAR WYE
744RSL4054
744RSS4292
130 °C/40 °C
4 BAR WYE
744FSM4374
130 °C/40 °C
4 BAR WYE
1020FDH5582
130 °C/40 °C
4 BAR WYE
1020FDH5582 1020FDH5582
130 °C/40 °C 130 °C/40 °C
4 BAR WYE
4 BAR WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
//ꢀ
Emissions – EPA Tier 2 Certified
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//ꢀ
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//ꢀ
Power Rating
//ꢀ
//ꢀ
Seismic Certification – Optional
– IBC Certification
– OSHPD Pre-Approval
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified