MODEL: 18JF  
Rack-mounted DCS Signal Conditioners 18-RACK  
POWER INPUT  
DC Power  
R: 24 V DC  
2-input MATH FUNCTION MODULE  
(field-programmable)  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
Functions & Features  
• Providing temperature or pressure compensation for a gas  
flow, and other arithmetic operations  
• Microprocessor based  
[2] OPTIONS  
Equation (Refer to the EQUATION table)  
/1: Temperature compensation for DP flowmeter (ideal gas)  
/2: Pressure compensation for DP flowmeter (ideal gas)  
/3: Addition/subtraction  
• Equation and parameters selectable on site via hand-held  
programmer PU-2x  
• Loop testing  
/4: Multiplication  
• Second channel output available at the front terminals  
and at the Standard Rack connector  
/5: Division  
EQUATION  
Equation parameters  
Typical Applications  
• Various flowmeters  
• Adding two flows  
X0: output (%)  
X
1
to X  
to K  
to A  
2
: input (%)  
• Ratio calculation  
K0  
2: gain ±29.999  
• Calculating average temperature  
A0  
2: bias (%) ±299.99 %  
EQUATION  
/1: Temperature compensation for DP flowmeter (ideal gas)  
K1X1  
X0 =  
K2X2+A2  
where X0 : compensated flow (linear characteristic)  
X1 : uncompensated flow (square root extraction available)  
X2 : temperature  
/2: Pressure compensation for DP flowmeter (ideal gas)  
X0 = K1X1 K2X2+A2  
where X0 : compensated flow (linear characteristic)  
X1 : uncompensated flow (square root extraction available)  
X2 : pressure  
MODEL: 18JF–[1]66–R[2]  
/3: Addition/subtraction  
ORDERING INFORMATION  
• Code number: 18JF-[1]66-R[2]  
X0 = K0 {K1 (X1+A1) + K2 (X2+A2)} + A0  
/4: Multiplication  
Specify a code from below for each of [1] and [2].  
(e.g. 18JF-666-R/3)  
X0 = K0 (K1X1+A1) (K2X2+A2) + A0  
/5:Division  
Use Ordering Information Sheet (No. ESU-1980). Default  
setting will be used if not otherwise specified.  
0
K (K1X1+A1)  
(K2X2+A2)  
X0  
=
+ A0  
[1] INPUT  
Current  
RELATED PRODUCTS  
• Programming Unit (model: PU-2x)  
A: 4 – 20 mA DC (Input resistance 100 Ω)  
Voltage  
• PC configurator software (model: JXCON)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
OUTPUT 1  
Voltage  
6: 1 – 5 V DC (Load resistance 2000 Ω min.)  
OUTPUT 2  
Voltage  
6: 1 – 5 V DC (Load resistance 2000 Ω min.)  
18JF SPECIFICATIONS  
ES-1880 Rev.11 Page 1/3  
http://www.m-system.co.jp/  

与18JF-A66-R/5相关器件

型号 品牌 获取价格 描述 数据表
18JFX MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-666-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-A66-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-H66-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-U166-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-U266-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-U366-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA-166-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA-266-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK