MODEL: 18JPA
Rack-mounted DCS Signal Conditioners 18-RACK
OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
FREQUENCY TRANSMITTER
(field-programmable)
Functions & Features
OUTPUT 2
• Converting the output from a pulse-type transducer into
two standard process signals
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
• Microprocessor based
• Field-programmable frequency range
• Linearization available for flow compensation
• Averaging non-uniform pulses
POWER INPUT
DC Power
R: 24 V DC
• Excitation
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Loop testing via hand-held programmer PU-2x
• Second channel output available at the front terminals
and at the Standard Rack connector
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Typical Applications
• Positive displacement flowmeters, turbine flowmeters and
vortex flowmeters
• Proximity switches
• Oval flowmeters
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
Output 1: Connector
Output 2: M3.5 screw terminals (torque 0.8 N·m)
and connector
MODEL: 18JPA–[1]66–R
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
ORDERING INFORMATION
• Code number: 18JPA-[1]66-R
Isolation: Input to output 1 to output 2 to power
Overrange output: -10 – +120 % at 1 – 5 V
(0 – 120 % when 0 % input equals to 0 Hz.)
Linearization: 16 points max. represented as percentage of
full-scale
Specify a code from below for [1].
(e.g. 18JPA-266-R)
• Frequency range (e.g. 0 – 152.3 Hz)
• Linearization data (max. 16 points)
Use Ordering Information Sheet (No. ESU-1673) to specify
linearization data when the I/O signals are non-linear.
Note: Consult factory on applications with a sensor handling
periodically (& quickly) changing frequency (e.g. oval
flowmeter).
Adjustments: Programming Unit (model: PU-2x); input
range, low-end cutout, zero and span, simulating output,
averaging nonuniform pulses, linearization data, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
Low-end cutout: 0 – 100 % adjustable (factory set to 0 %);
hysteresis fixed to 1 %
[1] INPUT
1: Open collector (Excitation: 12 V @ 30 mA)
2: Voltage pulse (Excitation: 12 V @ 30 mA)
3: Mechanical contact (Excitation: 12 V @ 30 mA)
INPUT SPECIFICATIONS
Excitation: 12 V DC @30 mA; shortcircuit protection
Pulse width (time) requirement: 10 msec. min. at
< 20 Hz; duty ratio 20 – 80 % at ≥ 20 Hz
18JPA SPECIFICATIONS
ES-1873 Rev.10 Page 1/3
http://www.m-system.co.jp/