描述
Rack-mounted DCS Signal Conditioners 18K-RACK

18KDY 数据手册

 浏览型号18KDY的Datasheet PDF文件第2页浏览型号18KDY的Datasheet PDF文件第3页 
MODEL: 18KDY  
Rack-mounted DCS Signal Conditioners 18K-RACK  
[2] OPTIONS  
Power Switch  
blank: None  
CURRENT LOOP SUPPLY  
Functions & Features  
/S: With power switch  
/SL: With power switch (with green LED)  
• Powering a 4 – 20 mA DC current loop  
• Shortcircuit protection  
• Applicable to smart transmitters  
• Usable as Isolator for 4 – 20 mA DC signals  
• Module can be retracted without removing wiring for an  
insulation test  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
• Power switch optional  
Connection  
Input: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Typical Applications  
• Various 2-wire transmitters  
Output 1: Connector  
Output 2: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Input to output 1 to output 2 to power  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
SUPPLY OUTPUT  
MODEL: 18KDY–A6[1]–R[2]  
Output voltage: 24 – 28 V DC with no load  
Current rating: ≤ 22 mA DC  
Shortcircuit Protection  
ORDERING INFORMATION  
• Code number: 18KDY-A6[1]-R[2]  
Specify a code from below for each of [1] and [2].  
(e.g. 18KDY-A66-R/SL)  
Current limited: 35 mA max.  
Protected time duration: No limit  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
INPUT  
Current  
A: 4 – 20 mA DC (Input resistance 276 Ω)  
OUTPUT SPECIFICATIONS  
The output goes below 0 % when the input is open.  
OUTPUT 1  
Voltage  
INSTALLATION  
Current consumption:  
6: 1 – 5 V DC (Load resistance 2000 Ω min.)  
Approx. 65 mA with voltage output  
(approx. 70 mA with /SL)  
[1] OUTPUT 2  
Approx. 95 mA with current output  
(approx. 100 mA with /SL)  
Current  
A: 4 – 20 mA DC (Load resistance 600 Ω max.)  
Voltage  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18KBXx  
Weight: 150 g (0.33 lb)  
6: 1 – 5 V DC (Load resistance 2000 Ω min.)  
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
18KDY SPECIFICATIONS  
ES-0426 Rev.7 Page 1/3  
http://www.m-system.co.jp/  

与18KDY相关器件

型号 品牌 获取价格 描述 数据表
18KDY-A66-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDY-A66-R/S MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDY-A66-R/SL MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDY-A6A-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDY-A6A-R/S MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDY-A6A-R/SL MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDYH2 MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDYH2-A6A-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDYH2-A6A-R/B MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK
18KDYH2-A6A-R/RE MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18K-RACK