描述
Rack-mounted DCS Signal Conditioners 18-RACK

18JFX 数据手册

 浏览型号18JFX的Datasheet PDF文件第2页浏览型号18JFX的Datasheet PDF文件第3页 
MODEL: 18JFX  
Rack-mounted DCS Signal Conditioners 18-RACK  
OUTPUT 1  
Voltage  
6: 1 – 5 V DC (Load resistance 2000 Ω min.)  
LINEARIZER  
(field-programmable)  
Functions & Features  
OUTPUT 2  
• Accepting non-linear input and providing two linearized  
outputs, proportional to the process variables  
• Micro-processor based  
Voltage  
6: 1 – 5 V DC (Load resistance 2000 Ω min.)  
• On-site calibration up to 16 points using a hand-held  
programmer PU-2x  
POWER INPUT  
DC Power  
• Field-programmable input range  
• Second channel output available at the front terminals  
and at the Standard Rack connector  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
RELATED PRODUCTS  
Typical Applications  
• Programming Unit (model: PU-2x)  
• V-notch weir  
• PC configurator software (model: JXCON)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
• Gas analyzer  
• Irregular-shaped tank level input for volume calculation  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
MODEL: 18JFX–[1]66–R  
Connection  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output 1: Connector  
ORDERING INFORMATION  
• Code number: 18JFX-[1]66-R  
Output 2: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Specify a code from below for [1].  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Input to output 1 to output 2 to power  
Linearization: 16 points max. within the range of -15.00 –  
+115.00 % input or output; represented as percentage of  
full-scale  
(e.g. 18JFX-666-R)  
Use Ordering Information Sheet (No. ESU-1669) to specify  
linearization data when the I/O signals are non-linear.  
• Linearization data (max. 16 points)  
• Special input range (For codes U1, U2 & U3)  
Adjustments: Programming Unit (model: PU-2x)  
(Refer to the users manual of JXCON for the adjustments  
configurable with JXCON.)  
[1] INPUT  
Current  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
H: 10 – 50 mA DC (Input resistance 100 Ω)  
Voltage  
• Linearization data  
• Input range  
• Zero and span  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
U1: Range ±100 mV;  
• Simulating output  
• Others  
(Minimum span 3 mV, Input resistance 20 kΩ min.)  
U2: Range ±1000 mV;  
Input range can be changed with Codes U1, U2 or U3 and  
limited within ranges of each code type.  
(Minimum span 30 mV, Input resistance 20 kΩ min.)  
U3: Range ±10 V;  
(Minimum span 0.3 V,Input resistance 1 MΩ min.)  
18JFX SPECIFICATIONS  
ES-1872 Rev.9 Page 1/3  
http://www.m-system.co.jp/  

与18JFX相关器件

型号 品牌 获取价格 描述 数据表
18JFX-666-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-A66-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-H66-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-U166-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-U266-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JFX-U366-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA-166-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA-266-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK
18JPA-366-R MSYSTEM

获取价格

Rack-mounted DCS Signal Conditioners 18-RACK