1页 80K
描述
Circuit Breakers 0.1-0.16A Motor Protector

15.901U 技术参数

生命周期:ActiveReach Compliance Code:unknown
风险等级:5.57电路保护类型:THERMAL CIRCUIT BREAKER
Base Number Matches:1

15.901U 数据手册

  
Altech Corp.  
Circuit Protection Devices  
MA Three Phase Adjustable Circuit Breakers Ñ  
35 mm DIN Rail Mount  
The Altech/ABL SURSUM MA holds through starting and inrush currents of three phase  
transformers, lighting, power supplies and motors (including the new high efficiency motors) yet  
provides tight overload protection, fast half-cycle short-circuit protection, and current/energy let-  
through protection.  
The MA is UL 508 Listed and UL¨ certified to CAN/CSA-C22.2 No. 14 (C-UL) as a manual motor  
controller with group ratings, and functions as a 3-phase disconnect, overload protector and  
controller in one compact DIN rail mounted package. It is a thermal/magnetic circuit breaker in the  
IEC style with thermal overload trip curves calibrated for USA norms. With the adjustment dial set at  
the full-load-amps (FLA) of the load, the MA/U cold-start trips in about one hour at an overload of  
115% FLA and in less than 10 seconds at 600% FLA, and hot-start trips in less than two minutes at  
150% FLA (i.e., Class 10 A overload device). The MA/U is therefore suitable overload protection for  
all motor applications covered under NFPA70 - National Electrical Code¨ 430-32 (a)(1), including  
those with service factors less than 1.15 or temperature rise over 40¡C. With screw-cage clamp  
terminals which accept 18 AWG to 3 AWG wire factory or field, the MA is particularly well suited for  
group applications and single motor taps under NEC¨ 430-53 (c) and (d).  
3¿ Horsepower Ratings at Nominal Line Voltage  
110-120 V 200 V 208 V 220-240 V 440-480 V  
EACH  
1-24  
Stock  
No.  
Mfr.Õs  
Type  
Cat.  
No.  
Rated  
Current  
FLA  
Dial Range  
Group  
SRT. CKT. Ratings  
6
501-4504  
501-6000  
501-4506  
501-6001  
501-4508  
501-4509  
501-4510  
MA0.16U  
MA0.25U  
MA0.40U  
MA0.63U  
MA1.0U  
MA1.6U  
MA2.5U  
15.901U  
15.902U  
15.903U  
15.904U  
15.905U  
15.906U  
15.907U  
0.16 A  
0.25 A  
0.40 A  
0.63 A  
1.00 A  
1.60 A  
2.50 A  
0.10 A-0.16 A  
0.16 A-0.25 A  
0.25 A-0.40 A  
0.40 A-0.63 A  
0.63 A-1.00 A  
1.00 A-1.60 A  
1.60 A-2.50 A  
Through MA2.5U, amp rated for motor circuits having a full load  
amperage (FLA) not exceeding the MAÕs general purpose rated  
current (RC, equals maximum dial setting) and a locked rotor  
current not exceeding 6 times the MAÕs RC.  
42 kARMS symmetrical  
(max. 1200 A MCCB or RK5)  
81.50  
81.50  
81.50  
81.50  
81.00  
81.50  
81.50  
1
3
3
3
501-4511  
501-4512  
501-4513  
501-4514  
MA4.0U  
MA6.3U  
MA10U  
MA16U  
15.908U  
15.909U  
15.910U  
15.911U  
4.00 A  
6.30 A  
10.00 A  
2.50 A-4.00 A  
4.00 A-6.30 A  
6.30 A-10.00 A  
10.00 A-16.00 A  
/
/
2
4
/
2
4
/
2
4
1
2
3
5
14 kARMS symmetrical  
(max. 350 A MCCB or RK5)  
81.50  
81.50  
81.50  
89.20  
11/  
2
3
11/  
2
3
11/  
3
2
1
2
16.00 A  
5
10  
501-4515  
501-4516  
501-4517  
501-4518  
MA20U  
MA25U  
MA32U  
MA40U  
15.912U  
15.913U  
15.914U  
15.915U  
20.00 A  
25.00 A  
32.00 A  
40.00 A  
16.00 A-20.00 A  
20.00 A-25.00 A  
25.00 A-32.00 A  
32.00 A-40.00 A  
3
3
5
5
5
5
71/  
5
5
10  
15  
20  
25  
10 kARMS symmetrical  
(max. 350 A MCCB or RK5)  
92.20  
98.30  
107.70  
119.80  
71/  
71/  
2
2
71/  
2
2
10  
10  
10  
10  
FI Earth Leakage Circuit Breakers Ñ  
35 mm DIN Rail Mount  
Accessories  
V-EA Touch Protectors  
Compact DIN rail mount Earth Leakage Circuit Breakers detect and  
interrupt ground faults. They are VDE approved for the European system  
of protecting people, animals, equipment and property from dangerous  
line-to-ground and shock hazard currents.  
Trip-capable on decayed line voltage, marked approval of DIN/VDE,  
marked ÒSnowflakeÓ temperature range, marked trip sensitivity to pulsed  
as well as sinusoidal fault currents, integral test circuit, insensitive to  
vibration, etc.  
US applications include ground fault protection of equipment (GFPE) using  
the 10 mA and 30 mA fault current ratings, especially when high  
distributed capacitance or other leakage cause excessive nuisance trips at  
lower fault currents. Applications for the 300 mA rating are equipment  
protection and fire prevention by limiting the energy of a fault to less than  
the minimum ignition energy for many materials.  
The V-EA protects against electrical shock during manual  
actuation in accordance with VDE 0106/Part 100 and VDE  
0470/Part 1, with Òfinger safeÓ terminal-screw heads and Òback  
of handÓ safe terminals. If additional ÒtouchÓ protection is  
desired, separate touch protector covers can easily be snapped  
on to the V-EA top and/or bottom terminals.  
The FI is not intended to repeatedly make/break currents above rated line  
current. Breaking capacity is 1500 A for rated line currents through 40 A  
and 2000 A for 63 A line. Limit let-through to 30,000 A2s for FI-2 and  
80,000 A2s for FI-4, or use gL fuses for 10 kA withstand capacity:  
16 A line = 63 A fuse; 25 A and 40 A line = 80 A fuse; 63 A line = 100 A fuse.  
Two Pole Single Phase 240 VAC Max.  
501-5120. 15.961. V-EA Bottom Terminals...............EACH .63  
501-5121. 15.962. V-EA Top Terminals.....................EACH .63  
Rated  
Line  
Current  
Fault  
Trip  
Current  
EACH  
1-24  
Stock  
No.  
Mfr.Õs  
Type  
Cat.  
No.  
Lock-Outs  
501-4519  
501-4520  
501-4521  
501-4522  
501-4523  
501-6002  
501-6003  
FI21.01  
FI22.03  
FI22.30  
FI23.03  
FI23.30  
FI22.03Y  
FI23.03Y  
15.921  
15.922  
15.924  
15.923  
15.925  
15.932*  
15.934*  
16 A  
25 A  
25 A  
40 A  
40 A  
25 A  
40 A  
10 mA  
30 mA  
300 mA  
30 mA  
300 mA  
30 mA  
190.00  
140.00  
170.00  
160.00  
170.00  
190.00  
220.00  
300 mA  
Four Pole Two/Three Phase 415 VAC Max.  
501-4524  
501-4525  
501-4526  
501-6004  
501-4528  
501-4529  
501-6005  
501-6006  
501-6007  
FI42.03  
FI42.30  
FI43.03  
FI43.30  
FI44.03  
FI44.30  
FI42.03Y  
FI43.03Y  
FI44.03Y  
15.926  
15.929  
15.927  
15.930  
15.928  
15.931  
15.933*  
15.935*  
15.936*  
25 A  
25 A  
40 A  
40 A  
63 A  
63 A  
25 A  
40 A  
63 A  
30 mA  
300 mA  
30 mA  
300 mA  
30 mA  
300 mA  
30 mA  
30 mA  
30 mA  
155.00  
160.00  
160.00  
170.00  
320.00  
230.00  
210.00  
220.00  
370.00  
Prevent inadvertent resetting of the V-EA or MA during  
maintenance.  
501-5122. 15.969. Lock-Out......................................EACH 4.30  
*With auxiliary contacts.  
For Fast, Dependable Service, Make Just One Call Ñ 1-800-433-5700  
ALLIED  
c
275  

与15.901U相关器件

型号 品牌 获取价格 描述 数据表
15/25-85555 EPCOS

获取价格

Aluminum Electrolytic Capacitor, Polarized, Aluminum, 25V, 20% +Tol, 20% -Tol, 15uF
15/408X046 EPCOS

获取价格

CAP,AL2O3,15UF,40VDC,20% -TOL,20% +TOL
15/X/10BLACK6A ETC

获取价格

KABEL WENDEL 3ADRIG 0.75QMM SCHW
15/X/10WHITE6A ETC

获取价格

KABEL WENDEL 3ADRIG 0.75QMM WEISS
15/X/11BLACK1A ETC

获取价格

KABEL WENDEL 3ADRIG 0.20QMM SCHW
15/X/11WHITE1A ETC

获取价格

KABEL WENDEL 3ADRIG 0.20QMM WEISS
15/X/9BLACK13A ETC

获取价格

KABEL WENDEL 3ADRIG 1.25QMM SCHW
15/X/9WHITE13A ETC

获取价格

KABEL WENDEL 3ADRIG 1.25QMM WEISS
150 PRODUCTWELL

获取价格

SHIELDED SMT POWER INDUCTORS
150 LITTELFUSE

获取价格

MINIATURE FUSES - 5x15 mm