MODEL: 10PP
High-density Signal Conditioners 10-RACK
[3] OUTPUT 2
0: None
2: Open collector (max. 10 kHz)
PULSE ISOLATOR
Functions & Features
• Galvanically isolating pulse rate signals
• Input frequency = output frequency
• Various outputs (relay, open collector and voltage pulses)
• Optional second channel output available at the front
terminals and at the Standard Rack connector
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[4] OPTIONS
blank: none
Typical Applications
• Isolating field pulse signals in order to reduce noises
• Changing e.g. dry contact signal to e.g. 5 V signals
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals at the front and via card-edge connector at the
rear; terminal cover provided
Connection: M3.5 screw terminals (torque 0.8 N·m) and
card-edge connector
MODEL: 10PP–[1][2][3]–R[4]
Power input: Supplied from card-edge connector
Screw terminal: Nickel-plated steel
ORDERING INFORMATION
• Code number: 10PP-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
(e.g. 10PP-332-R/Q)
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Frequency range: Input and output are the same.
Chattering protection: Filter provided for mechanical
contact input
• Frequency range (e.g. 0 – 1000 Hz)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT SPECIFICATIONS
Excitation: 12V DC ±2 V @ 30 mA; shortcircuit protection
■ Open Collector
Note: Output 1 and 2 frequency is equal.
[1] INPUT
Maximum frequency: 10 kHz
1: Mechanical contact (max. 30 Hz)
2: Open collector (max. 10 kHz)
3: Voltage pulse (max. 10 kHz)
Pulse width time requirement: 10 μsec. min. for ON and OFF
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 200 Ω / 3.5 V for ON, ≥ 100 kΩ / 7 V for OFF
■ Mechanical Contact
Maximum frequency: 30 Hz
[2] OUTPUT 1
Pulse width time requirement: 10 msec. min. for ON and
OFF
1: Low frequency open collector (max. 30 Hz)
2: High frequency open collector (max. 10 kHz)
3: 5 V pulse (max. 10 kHz)
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 200 Ω / 3.5 V for ON, ≥ 100 kΩ / 7 V for OFF
■ Voltage Pulse
4: 12 V pulse (max. 10 kHz)
5: 24 V pulse (max. 10 kHz)
Maximum frequency: 10 kHz
8: Photo MOSFET relay pulse (max. 30 Hz)
Pulse width time requirement: 10 μsec. min. for high and
low levels
10PP SPECIFICATIONS
ES-0861 Rev.9 Page 1/4
http://www.m-system.co.jp/