General Purpose Relays
Special Load PCB Relay RP 3 SL
I
I
I
I
I
I
1 pole 16 A, 1 NO contact
For high inrush currents,
120 A / 20 ms inrush peak current
Mono- or bistable
4 kV / 8 mm coil-contact
RoHS compliant (Directive 2002/95/EC)
as per product date code 0404
Applications
Lighting control, timers, motor control, building automation
F0147-A
Approvals
V
REG.-Nr. 3736 (DC versions only),
Z
E214024,
H
2011340.05 (DC vers. only)
Technical data of approved types on request
Contact data
Contact configuration
Contact set
1 NO
single contact
micro-disconnection
16 A
Type of interruption
Rated current
Rated voltage / max.switching voltage AC
Limiting continuous current
Maximum breaking capacity AC
Limiting making capacity, max 4 s, duty factor 10%
peak value, max 20 ms
Contact material
Mechanical endurance DC
bistable
Rated frequency of operation with / without load
240/400 VAC
16 A
4000 VA
25 A
120 A
AgSnO2
> 20x106 cycles
> 1x 106 cycles
16 / 1200 min-1
Contact ratings
Type
Load
Cycles
5x104
1x105
RP3SL 16 A, 250 VAC, 70°C, 16 min-1, IEC61810-1
RP3SL 12 A, 250 VAC, 70°C, 16 min-1, IEC61810-1
Coil data
Coil data, monostable coil
Rated coil voltage range
Coil power
5...110 VDC
typ 520 mW
2 / 1
Operative range RTII / RTIII
Coil versions, DC-coil
Coil
Rated
voltage
VDC
12
Operate
voltage
VDC
Release
voltage
VDC
1.2
Coil
resistance
c
270+10%
1100+15%
4400+15%
6540+15%
Rated coil
code
power
mW
533
012
024
048
060
9.0
24
18.0
2.4
524
48
36.0
4.8
6.0
524
60
45.0
550
All figures are given for coil without preenergization, at ambient temperature +23°C
Other coil voltages on request
1
Datasheet
Rev. EK1
Dimensions are in mm unless
otherwise specified and are
shown for reference purposes
only.
Product specification
processing information
only to be used together
with the 'Definitions' at
schrackrelays.com in the
‘Schrack’ section.
Issued 2005/11
according to IEC 61810-1.
Product data, technical para-
meters, test conditions and
www.tycoelectronics.com
www.schrackrelays.com
Specifications subject to
change.