XP95-T
Description
Analog Addressable Thermal Sensor
The Gamewell-FCI XP95-T Analog Addressable Thermal
Sensor operates with the Gamewell-FCI 600 Series analog
addressable fire alarm control panels (FACPs). The Series
XP95-T thermal sensor digitally transmits its address and
the chamber’s analog temperature value to the FACP for
analysis.
Thermal sensors are readily distinguished from smoke by
the open webs in the housing designed to allow for free
movement of air around the exposed thermistor.
Operation
XP95-T
The XP95-T thermal sensor constantly monitors its sens-
ing element as well as its internal electronics. The results
are digitally reported along with the unit’s address through
the integral communication electronics located in the sen-
sor head. The thermal sensor monitors temperature by
using a single thermistor network which provides a voltage
output proportional to the external air temperature. This
signal is processed and conditioned by an on-board
advanced technology ASIC that digitally transmits the
ambient temperature data to the FACP when interrogated.
Features
•
•
Compatible with the Gamewell-FCI 600 Series analog
addressable control panels
Fits 4.0" (10.16 cm) or 6.0" (15.24 cm) ultra low–profile,
and E-Z fit bases
•
•
•
•
•
•
•
•
Audible alarm sounder base
Trouble and Alarm conditions of the XP95 sensors are
determined at the FACP. The status information of each
sensor is analyzed for off–normal conditions by the control
panel. If the sensor reports a condition that matches its
programmed trouble signature, the FACP will report that
the sensor is in trouble and will follow its programmed
response sequence. Likewise, if the status reported
matches the alarm signature, the FACP will follow the pro-
grammed alarm response for the specific device in alarm.
When a sensor is in alarm, the integral LED in the sensor’s
housing will light continuously.
Address is stored in the sensor base
Address is set by XPert addressing card
Two-color status LED
Fixed point or rate-of-rise functions
Timed tempe rature in cre ase cau ses an a larm
Thermal adjustability programming
Optional remote LED
The XP95-T thermal sensor is calibrated to return a normal
air temperature analog value to the FACP at 77º F. The
device connects to a two–wire loop circuit carrying both
data and a 117 to 28 VDC supply voltage, and is insensi-
tive to loop connection polarity.
An ISO 9000-2000 Company
SIGNALING
FM
APPROVED
S2527
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2055 Rev. a1 page 1 of 2