Product data sheet
Characteristics
XB4BA3351
black flush complete pushbutton Ø22 spring
return 1NO "down arrow"
Main
Commercial Status
Commercialised
Harmony XB4
Range of product
Product or component
type
Complete push-button
Device short name
Bezel material
XB4
Chromium plated metal
Fixing collar material
Mounting diameter
Zamak
0.87 in (22 mm)
1
Sale per indivisible
quantity
Shape of signaling unit
head
Round
Type of operator
Operator profile
Spring return
Black flush, white down arrow
1 NO
Contacts type and
composition
Contacts operation
Slow-break
Connections - terminals
Screw clamp terminals: 1 x 0.22...2 x 2.5 mm² without
cable end conforming to EN/IEC 60947-1
Screw clamp terminals: <= 2 x 1.5 mm² with cable end
conforming to EN/IEC 60947-1
Complementary
Product weight
0.18 lb(US) (0.08 kg)
Resistance to high pressure washer
Contacts usage
1015.26 psi (7000000 Pa) at 131 °F (55 °C),distance: 0.1 m
Standard contacts
Positive opening
Without positive opening
Operating travel
0.17 in (4.3 mm) (total travel)
0.1 in (2.6 mm) (NO changing electrical state)
Operating force
3.8 N (NO changing electrical state)
5000000 cycles
Mechanical durability
Tightening torque
Shape of screw head
7.08...10.62 lbf.in (0.8...1.2 N.m) conforming to EN 60947-1
Slotted head compatible with flat Ø 5.5 mm screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Cross head compatible with pozidriv No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver
Contacts material
Silver alloy (Ag/Ni)
Short circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
10 A conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
[Ie] rated operational current
600 V (degree of pollution: 3) conforming to EN/IEC 60947-1
6 kV conforming to EN/IEC 60947-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Apr 28, 2016
1