Metal-OxideVaristors (MOVs)
Radial Lead Varistors > C-III Varistor Series
RoHS
C-III Varistor Series
Description
The C-III Varistor Series of Metal-Oxide Varistors (MOVs)
are specifically designed for applications requiring high
surge energy absorption ratings and superior multiple
pulse absorption rating. This is achieved through a special
dielectric material formulation which also results in
higher repetitive surge ratings than other MOV types.
The C-III Varistor Series is primarily intended for use in
AC line Surge Protection Device (SPD) product and other
similar applications requiring high transient energy and
peak current capability in a relatively small package size.
Agency Approvals
Features
Agency File
Number
Agency
Agency Approval
• Lead–free, Halogen-
Free and RoHS
compliant
• Available in tape and
reel for automatic
UL1449
E320116
116895
91788
insertion; Also available
with crimped and/or
trimmed lead styles
CECC 42201-006
IEC 61051-1
IEC 61051-2
• High energy
absorption capability
• No derating up to
85ºC ambient
WTM 40J to 530J (2ms)
IEC 60950-1 (Annex Q) for 14mm
and 20mm only
• High pulse life rating
• The C-III Series is
supplied in 10mm,
14mm and 20mm
disc versions with
various lead options
C22.2 No. 8
• High peak pulse
current capability
CECC 42201-006
IEC 61051-1
IEC 61051-2
I
TM 3500A to
E1273/F
10,000A (8/20µs)
• Wide operating
voltage range
IEC 60950-1 (Annex Q) for 14mm
and 20mm only
VM(AC)RMS 130V to 1000V
Additional Information
Datasheet
Resources
Samples
Absolute Maximum Ratings
• For ratings of individual members of a series, see Device Ratings and Specifications chart
Continuous
C-III Series
Units
Steady State Applied Voltage:
AC Voltage Range (VM(AC)RMS
)
130 to 1000
V
Transients:
Single-Pulse Peak Current (ITM) 8/20µs Wave
(See Peak Pulse Current Test Waveform)
3500 to 10,000
A
Single-Pulse Energy Range (WTM)2ms Rectangular Wave
Operating AmbientTemperature Range (TA)
40 to 530
-55 to +85
-55 to +125
<0.01
J
ºC
StorageTemperature Range (TSTG
)
ºC
Temperature Coefficient (aV) of Clamping Voltage (VC) at SpecifiedTest Current
Hi-Pot Encapsulation (COATING Isolation Voltage Capability)
COATING Insulation Resistance
%/ºC
V
2500
1000
MΩ
CAUTION: Stresses above those listed in "Absolute Maximum Ratings" may cause permanent damage to the device. This is a stress only rating and operation of the device at these or
any other conditions above those indicated in the operational sections of this specification is not implied.
© 2018 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 10/31/18