Industrial Power Supplies
TSP-WR Series
180–600 Watt
TSP–BCM24 Battery Controller Module
This module provides a professional battery management system to charge and
monitor an external lead-acid battery. Together with a power supply of the TSP
series, a perfect DC-UPS system can be configured. The connected battery will
be charged and held in charged mode by the power supply. In the event of a
mains power failure the battery will supply the output power until the battery is
discharged. As a consequence, the output voltage of the system is equivalent to the
battery voltage. To avoid overcharging the battery, an external temperature sensor
adjusts the battery voltage automatically to the required end of charge voltage. This
can extend the battery life.
The battery is protected against deep discharge. Mains power and battery status
are monitored regularly and failures indicated by corresponding LED’s and alarm
outputs. The module also provides an external On/Off input to switch-off both,
power supply and battery.
Models
Order code
(includes terminal plugs)
Inputs
Input Power
max
Output Voltage
nom.
*Output Power
max.
TSP-BCM24
360 W
600 W
360 W
24 VDC Power Supply
and 24 VDC Battery
24 VDC
TSP-BCM24H
600 W
*reduce max. output current by battery charging current
Function Diagram
Connector Positions
Front view
Bottom view
Top view
+
J1.2
J2.3
J2.4
+
_
- - + +
Output
Load
DC IN
_
J1.1
J2.1
J2.2
Fuse
J3.1
J3.2
Output
Volt adjust
+
_
J1.4
Remote
Link
TSP
J1.3
Power
Supply
24V Battery
Battery Controller
AC OK
Bat. OK
DC OK
Remote On/Off
Remote Link
DC IN Battery
Temp. Sensor
(TS)
J5.1
J5.2 J5.3
J5.4 J5.5
J5.6
J5.7 J5.8
J5.9
J5.10
T
Temp.
Sensor (TS)
DC-OK BAT.-OK DC-OK Remote
input output On/Off
- + - +
Specifications
Operating temperature
– 25 °C to +70 °C max. (–13 °F to +158 °F)
derating above 40 °C (104 °F): 1.5 %/K
Electromagnetic compatibility
Battery protection
in correspondence to connected units (no internal
switching device)
over voltage, deep discharge, short circuit- and
revers connection (built-in fuse)
Status signals
DC-OK input, DC-OK output, BAT OK
all relay contact closed at status OK
Rating per relay contact
Dimensions
30 VDC/1.0 A max.
see page 8
Remote link cable (0.5m)
Remote On/Off
1 cable included with TSP-BCM24 module
by ext. contact: contact open = On, contact closed = Off
www.tracopower.com/products/tsp-bcm_inst.pdf
Installation instructions
http://www.tracopower.com
Page 6 of 11