Industrial Power Supplies
TSP-WR Series
180–600 Watt
General Specifications
Isolation
according to IEC/EN 60950-1, UL 60950-1, UL 508
Safety standards
– Information technology equipment
– Industrial control equipment
– Electrical equipment of machines
– Electronic equipment for power installation
– Safety transformers for SMPS
IEC/EN 60950-1, UL 60950-1, CSA-C22.2 No. 60950-1-03
UL 508C, CSA-C22.2 No. 107
EN 60204
EN 50178
EN 61558-2-4
Safety approvals
and certifications
– CB report
for IEC 60950-1
www.tracopower.com/products/tsp-wr-cb.pdf
UL 60950-1 rec. File: E181381, UL 508C listed File: pending
www.ul.com -> certifications
– UL approvals
– CSA certification
(file no. 219759) for UL 60950-1
CSA-22.2 No. 60950-1-03, CSA C22.2 No. 107.1-01
www.tracopower.com/products/tsp-wr-csa.pdf
for IEC/EN 60950-1, EN 60204, EN 61558-2-4
www.tracopower.com/products/tsp-wr-gs.pdf
– GS certification
Safety class
Degree of electrical protection I (IEC 536)
IP 20 (IEC 529)
Case protection
Electromagnetic compatibility (EMC), Emissions
– Conducted RI suppression on input
– Radiated RI suppression
Electromagnetic compatibility (EMC), Immunity
IEC/EN 61000-6-3, IEC/EN 61204-3
EN 55011 class B, EN 55022 class B,
EN 55011 class B, EN 55022 class B,
IEC/EN 61000-6-2, IEC/EN 61204-3
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity
– Immunity to conducted RF disturbances
– Power frequency field immunity
– Voltage dips
IEC / EN 61000-4-2
IEC / EN 61000-4-3
IEC / EN 61000-4-4
IEC / EN 61000-4-5
IEC / EN 61000-4-6
IEC / EN 61000-4-8
IEC / EN 61000-4-11
4 kV / 8 kV
10 V / m
2 kV
1 kV / 2 kV
10 V
30 A / m
Environment
– Vibration acc. IEC 60068-2-6;
– Shock acc. IEC 60068-2-27
3 axis, sine sweep, 10-55 Hz, 1g, 1oct/min
3 axis, 15 g half sine, 11 ms
Enclosure material
Mounting
aluminium (chassis) / zinc plated steel (cover)
– DIN-rail mounting
for DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
– Wall mounting (option)
with wall mounting bracket - see page 10
Connection
detachable screw terminals (plugs included)
2 terminals per output
Output Power Derating
A)
Output Power Derating
vs Ambient Temperature
B)
Output Power Derating
vs Input Voltage
100
90
100
90
TSP 600
TSP 600
80
80
TSP 180
TSP 360
70
70
TSP 180
TSP 360
60
50
40
30
20
10
60
50
40
30
20
10
0
0
-25
40
50
60
70
85
100
115
132
187
284 323
550
Temperature [˚C]
Input Voltage [VAC]
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.