480W Single Output Industrial DIN RAIL with PFC Function
SDR-480 series
Features :
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.94
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
PQ
GL
SPECIFICATION
MODEL
SDR-480-24
SDR-480-48
DC VOLTAGE
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
20A
0 ~ 20A
10A
0 ~ 10A
480W
15A
480W
30A
Note.6 720W (3sec.)
OUTPUT
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 1.2%
120mVp-p
48 ~ 55V
1.0%
24 ~ 28V
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
0.5%
0.5%
1.0%
1.0%
1500ms, 150ms/230VAC
14ms/230VAC at full load
3000ms, 150ms/115VAC at full load
VOLTAGE RANGE
Note.7 90 ~ 264VAC
127 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
47 ~ 63Hz
0.94/230VAC
94%
0.99/115VAC at full load
INPUT
5A/115VAC
40A/115VAC
<0.8mA / 240VAC
2.5A/230VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
80A/230VAC
LEAKAGE CURRENT
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
OVERLOAD
56 ~ 65V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
105 (TSW : detect on heatsink of power switch)
29 ~ 33V
OVER VOLTAGE
PROTECTION
5
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
-25 ~ +70 (Refer to "Derating Curve")
Note.5
FUNCTION DC OK REALY CONTACT RATINGS (max.)
WORKING TEMP.
20 ~ 95% RH non-condensing
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
TEMP. COEFFICIENT
VIBRATION
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
SAFETY &
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC
(Note 4)
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
SEMI F47, GL approved
EMC IMMUNITY
MTBF
112.9Khrs min. MIL-HDBK-217F (25
85.5*125.2*128.5mm (W*H*D)
1.6Kg; 8pcs/13.8Kg/0.9CUFT
)
OTHERS
NOTE
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:SDR-480-SPEC 2011-12-27