MODEL: SC110
blank: Single supply
Single Loop Controller Series
/M2: 100 – 240 V AC (dual supply)
(Operational voltage range 85 – 264 V AC; 50/60 Hz)
/R: 24 V DC (dual supply)
MULTI-FUNCTION PID CONTROLLER
(color LCD with touch-panel, MV output backup)
(Operational voltage range 24 V DC ±10 %;
ripple 10 %p-p max.)
Control/Backup modules are powered from common terminals
with 'single' supply type; powered from independent
terminals with 'dual' supply type.
Language
blank: Japanese
144
(5.67)
/E: English
(Language (Japanese or English) can be chosen by front
panel setting.)
*
mm (inch)
Configurator Interface
*Selectable with option code
blank: Infrared
/1: Stereo jack
(If external noise interference is a concern, stereo jack
type is recommended.)
MODEL: SC110–[1]0–[2][3]
Terminal block
ORDERING INFORMATION
• Code number: SC110-[1]0-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. SC110-10-M2/3/M2/E/1/T/Q)
blank: One block terminal
/T: Separable terminal
Other Options
blank: none
• Specify the specification for option code /Q
(e.g. /C01/S01)
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
[1] DISCRETE OUTPUT
1: Relay contact
2: Photo MOSFET relay
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
MODBUS
0:None
FUNCTIONS & FEATURES
Functions & Features
[2] POWER INPUT
AC Power
• Color LCD with touch panel
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)
• Five Operation views (digital display, bargraph, dual-loop
bargraph, short trend and user's parameter table views)
• Enhanced screen functions for engineering (configuration,
programming and tuning views)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Universal input x 2 points, analog input x 4 points,
discrete input x 6 points, pulse input x 5 points, high speed
pulse input x 1 point
[3] OPTIONS (multiple selections)
Housing Depth (must be specified)
/300: 300 mm (Discontinued, select /3)
/400: 400 mm (Discontinued, select /4)
/600: 600 mm (Discontinued, select /6)
/3: 300 mm
• Current output (4-20 mA) x 2 points, voltage output (1-5
V) x 2 points, relay or photo-MOSFET relay output x 5 points
• RUN contact output (relay) x 1 point
• Computation cycle selectable between 50 msec. and 3
sec. (control cycle selectable between 1 and 64 times of the
computation cycle)
/4: 400 mm
/6: 600 mm
Backup Module Power Supply
• Two PID function blocks
SC110 SPECIFICATIONS
ES-6339 Rev.17 Page 1/12
http://www.m-system.co.jp/