● UL/CSA and EN Safety certified
● EN-61010 for Test, Measurement and Lab Use
● EN-60601 for Medical Applications
● Reinforced Isolation 6.4kVDC or 8kVDC
● Optional Continuous Short Circuit Protected
● Compact SIP7 Package
ECONOLINE
DC/DC-Converter
with 3 year Warranty
Features
Unregulated
Converters
● Efficiency to 88%
● Very Low Isolation Capacitance
● /X2 Version with >9mm Input/Output Clearance
2 Watt
SIP 7 Single &
Dual Output
The RxxP2xxS_D Series of DC/DC Converters are certified to UL/CSA-60950 and UL/CSA
60601. This makes them ideal for medical and safety applications where approved or reinforced
isolation is required. The reinforced versions are also EN61010-1 certified for Lab Equipment.
The /X2 version has an input/output clearance of more than 9mm.
Description
Selection Guide
Part
Number
SIP 7
Reinforced
Isolation
(kVDC)
Input
Voltage
(VDC)
Output
Voltage
(VDC)
Output Efficiency
Max
Capacitive
Load(1)
Current
(mA)
Std
(%)
RxxP23.3S
RxxP205S
RxxP209S
RxxP212S
RxxP215S
RxxP23.3D
RxxP205D
RxxP209D
RxxP212D
RxxP215D
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
/R6.4 & /R8
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
5, 12, 15, 24
3.3
5
600
400
222
167
132
300
200
111
85
72-78
79-84
80-87
80-87
80-88
73-80
79-85
80-87
80-87
80-88
3300µF
1200µF
1200µF
680µF
680µF
1500µF
470µF
470µF
330µF
330µF
9
12
15
3.3
5
RoHS
2011/65/EU
6/6
E-314885
EN-60950-1 Certified
EN-60601-1 Certified
UL/CSA 60950-1 Certified
UL-60601 Certified
EN-61010-1 Certified
IEC-60601-1 CB Report
9
12
15
66
xx = Input Voltage. Other input and output voltage combinations available on request.
* add Suffix “P” for Continuous Short Circuit Protection, e.g. R05P205S/P, R05P205D/P
* add Suffix “/X2” for single output with alternative pinout, e.g. R05P205S/X2, R05P205S/P/X2
* add Suffix “/R6.4” or “/R8” for Reinforced Isolation, e.g. R05P205D/R6.4, R05P205S/P/X2/R8
RxxP2xx/R
Specifications (measured at T = 25°C, nominal input voltage, full load and after warm-up)
A
Input Voltage Range
10ꢀ
5ꢀ
Output Voltage Accuracy
Derating-Graph
Line Voltage Regulation
Load Voltage Regulation
(10ꢀ to 100ꢀ full load)
Output Ripple and Noise (20MHz BW)
Operating Frequency
1.2ꢀ/1ꢀ of Vin typ.
15ꢀ max.
3.3, 5V output types
other output types
(Ambient Temperature)
10ꢀ max.
200mVp-p max.
20kHz min. / 50kHz typ. / 85kHz max.
65ꢀ min. / 80ꢀ max.
100
80
Efficiency at Full Load
Minimum Load = 0ꢀ
Specifications valid for 10ꢀ minimum load only.
60
Isolation Voltage
/R6.4 (tested for 1 second)
6400VDC
3200VAC / 60Hz
8000VDC
Safe Operating Area
(rated for 1 minute**)
/R8 (tested for 1 second)
(rated for 1 minute**)
40
20
0
4000VAC / 60Hz
1.5pF min. / 10pF max.
15 GΩ min.
-40
0
50
100 150
Isolation Capacitance
Isolation Resistance
Short Circuit Protection
P-Suffix
85
Operating Temperature °C
1 Second
Continuous
continued on next page
**Any data referred to in this datasheet are of indicative nature and based on our practical experience only. For further details, please refer
to our Application Notes.
Refer to Application Notes
www.recom-power.com
E-100
REV: 2/2015