Circuit Breaker Accessories
C-Series Remote Operated Module
The Carling Technologies Remote Operated Circuit Breaker
(ROCB) combines the convenience of remote ON, OFF and
Reset capabilities, with the safety and accuracy of a standard
magnetic current sensing device, thus allowing operation of the
breaker from various locations in a system, facility or site (while
not sacrificing the ability to manually operate the breaker if
required). With the ROCB, service, diagnostics, load shedding
and power distribution control functions can now be performed
in areas that were previously unattended, inaccessible or
unsafe.
Design Features include:
• ON-OFF and trip indication
• Load shedding
• Energy management
• Compact size
• Automatic reset capable
• Choice of interface styles
• Panel or DIN rail mounting
• Manual Operation Override
• Fits into industry standard cut-out
The ROCB module allows remote operation of the C-Series
panel mount breaker, or the D-Series DIN rail mount breaker
(up to 3 poles) through hard wiring with a single pole, double
throw switch connected to a standard power source, or more
sophisticated relay and modem networks.
ROCB Motor Specifications:
• Voltage input: 12 VDC to 80 VDC
• Start current: < 1 amp
• Switching time: < 2 seconds
The ROCB module can be mounted to either side of the host
breaker, while occupying only the width of a standard C-Series
pole. Several interface methods are available. Remote physical
actuation of the host circuit breaker is achieved by connecting
the ROCB module’s handle with the breakers.
Being based on the C-Series breaker, the ROCB allows easy
adaptation into existing panel designs. In addition, its compact
size allows efficient use of space for new design applications.
With the ROCB, Carling has designed a versatile, compact and
reliable solution -- in a hydraulic/magnetic circuit breaker or
switch only device that can be operated both manually and
remotely.
To order a remote operated circuit breaker, add / plus the remote module part number to the end of the C-Series
circuit breaker catalog number. ex.CA1BO24620121C/RB1110BU1C
Match color & mounting inserts of breaker.
10
Lead Length
RB
/
1
B
U 1
1
C
7
1
3
5
6
2
4
8
Actuator
Color
Mounting
Insert
Series
Interface
Voltage
Rating
Mounting
Position
Agency
Approval
5 VOLTAGE RATING
1 SERIES
RB
A
B
C
12 VDC
20-40 VDC
41-80 VDC
2 MOUNTING POSITION
As viewed from back of breaker, line side up, pole 1 left.
6 ACTUATOR COLOR
0
1
2
n/a - ordered separate from breaker
Left Side
T
U
V
White
Black
Red
Right Side
3 INTERFACE
W
Yellow
1
2
3
4
Flying Leads
Integral Connector
Flying Leads w/ 4 pin dual row connector (female)
Flying Leads w/ 4 pin dual row connector (male)
7 MOUNTING INSERT
1
2
6-32 x 0.195”
ISO M3 x 5mm
4 LEAD LENGTH
8 AGENCY APPROVAL
00
01
02
03
04
05
06
07
08
09
10
No Lead
11
12
13
14
15
16
17
18
19
20
21
11”
12”
13”
14”
15”
16”
17”
18”
19”
20”
21”
22
23
24
25
26
27
28
29
30
22”
C
E
G
I
UL Recognized & CSA Accepted
TUV Certified, UL Recognized & CSA Accepted
UL 489 Listed & CSA Certified
UL 1500 Ignition Protected,UL Recognized & CSA Accepted
UL 489 Listed, CSA Certified & TUV Certified
1”
2”
3”
4”
5”
6”
7”
8”
9”
10”
23”
24”
25”
26”
27”
28”
29”
30”
J
Notes:
Available with integral connector only.
Integral and 4-pin dual row connectors not available with agency approval G: UL 489.
120