MODEL: R3-NFL1
■ COMMON MEMORY AREA 2
The following shows the data transmitted to the common memory area 2 from the network module.
• R3-NFLBLD Setting Example
Address
I/O module/ch
Description
0x0000 <== DI02.01 ... 16
Transmitting the R3-DA16 ch.1 through ch.16 data to the common memory area 2,
address 0x0000
0x0001 <== AO03.01
Transmitting the R3-YV4 ch.1 data to the common memory area 2, address 0x0001
Transmitting the R3-DC16 ch.1 through ch.16 data to the common memory area 2,
address 0x0002
0x0002 <== DO04.01 ... 16
• Data Frame
15
0
Top
Address +0
Module 2, Ch. 1...16
Module 3, Ch. 1
Module 4, Ch. 1...16
+2
■ OUTPUT MODULE
The output data at designated addresses of the common memory area are transmitted to the R3 series output modules.
• R3-NFLBLD Setting Example
I/O module/ch
< Module 3 >
AO03.01
Address
<== 1-0x0000
<== 1-0x0001
<== 1-0x0002
Description
Transmitting the data at the common memory area 1, address 0x0000 (R3-SV4 ch.1) to
the R3-YV4 ch.1
AO03.02
AO03.03
Transmitting the data at the common memory area 1, address 0x0001 (R3-SV4 ch.2) to
the R3-YV4 ch.2
Transmitting the data at the common memory area 1, address 0x0002 (R3-SV4 ch.3) to
the R3-YV4 ch.3
< Module 4 >
DO04.01
<== 2-0x0000-16 Transmitting the data at the common memory area 2, address 0x0000, 16th bit
(R3-DA16 ch.16) to the R3-DC16 ch.1
Note: When output data is allocated from the common memory, be sure to mount an output module.
Otherwise, an internal bus error is detected and PWR LED turns off.
MODULE STATUS, MODULE ERROR, DATA ERROR, SOURCE NODE ERROR
Shows each module's availability and error status.
15
0
Module 1
Module 2
Module 3
:
Module 16
R3-NFL1 SPECIFICATIONS
ES-8426 Rev.14 Page 6/9
https://www.m-system.co.jp/