R15
Industrial Electromagnetic Relays
• Contacts AgNi
• For plug-in sockets, 35 mm rail mount or on panel mounting.
• Cadmium-free contacts-R15 DPDT, R15 3PDT, R15 4PDT relays
• WT (mechanical indicator and lockable front test button) - standard features of
R15 DPDT, R15 3DPT relays in cover, for plug-in sockets.
• Relays may be provided with the test buttons (no latching) and plugs (see page 115).
• AUCOTEAM, GmbH Berlin - railway standards.
E105728
Contact Data
Number and type of contacts
Contact material
DPDT
AgNi
3PDT
AgNi
4PDT
AgCdO
Rated / max. switching voltage AC
Min. switching voltage
250 V / 440 V
10 V
250 V / 440 V
250 V / 440 V
10 V
10 V
Rated load (capacity)
AC1 10 A / 250 V AC; 10 A / 277 V AC UL 508
10 A / 250 V AC; 10 A / 277 V AC UL 508
10 A / 250 V AC; 10 A / 277 V AC UL 508
AC15
AC3
3 A / 120 V; 1.5 A / 240 V (B300)
3 A / 120 V; 1.5 A / 240 V (B300)
3 A / 120 V; 1.5 A / 240 V (B300)
370 W (single-phase motor.
370 W (single-phase motor.
370 W (single-phase motor.
1/2 HP / 240 V AC UL 508)
1/2 HP / 240 V AC UL 508)
1/2 HP / 240 V AC UL 508)
DC1
10 A / 24 V DC (see Fig. 3)
10 A / 24 V DC (see Fig. 3)
10 A / 24 V DC (see Fig. 3)
DC13
0.22 A / 120 V; 0.1 A / 250 V (R300)
0.22 A / 120 V; 0.1 A / 250 V (R300)
0.22 A / 120 V; 0.1 A / 250 V (R300)
Min. switching current
Max. inrush current
Rated current
Max. breaking capacity
Min. breaking capacity
Contact resistance
Max. operating frequency
• at rated load
5 mA
20 A
10A
2500 VA
0.3 W
≤ 100 mΩ
5 mA
20 A
10A
2500 VA
0.3 W
≤ 100 mΩ
10 mA
20 A
10A
2500 VA
0.5 W
≤ 100 mΩ
AC1
AC1
1200 cycles/hour
12000 cycles/hour
1200 cycles/hour
12000 cycles/hour
1200 cycles/hour
12000 cycles/hour
• no load
Coil Data
Rated voltage
50/60 Hz AC
DC
6 ... 240 V
6 ... 220 V
6 ... 240 V
6 ... 220 V
6 ... 240 V
6 ... 220 V
Must release voltage
Operating range of supply voltage
Rated power consumption
AC: ≥ 0.15 Un; DC: ≥ 0.1 Un
see page 68
AC: 2.8 VA 50 Hz; 2.5 VA 60 Hz; DC: 1.5 W
AC: ≥ 0.15 Un; DC: ≥ 0.1 Un
see page 68
AC: 2.8 VA 50 Hz; 2.5 VA 60 Hz; DC: 1.5 W
AC: ≥ 0.15 Un; DC: ≥ 0.1 U
see page 68
AC: 2.8 VA 50 Hz; 2.5 VA 60 Hz; DC: 1.5 W
v
Insulation
Insulation rated voltage
Rated surge voltage
Overvoltage category
Insulation pollution degree
Dielectric strength
• between coil and contacts
• contact clearance
• pole - pole
250 V AC
2500 V 1.2 / 50 µs
250 V AC
2500 V 1.2 / 50 µs
250 V AC
2500 V 1.2 / 50 µs
III
3
III
3
III
3
2500 V AC type of insulation: basic
1500 V AC type of clearance: micro-disco.
2000 V AC type of insulation: basic
2500 V AC type of insulation: basic
1500 V AC type of clearance: micro-disco.
2000 V AC type of insulation: basic
2500 V AC type of insulation: basic
1500 V AC type of clearance: micro-disco.
2000 V AC type of insulation: basic
Contact - coil distance
• clearance
≥ 3 mm
≥ 3 mm
≥ 3 mm
• creepage
≥ 4.2 mm
≥ 4.2 mm
≥ 3.2 mm
General Data
Operating / release time (typical)
Electrical life
• resistive AC1
• cos
Mechanical life (cycles)
Dimensions (L x W x H)
Weight
AC: 12 ms / 10 ms; DC: 18 ms / 7 ms
AC: 12 ms / 10 ms; DC: 18 ms / 7 ms
AC: 12 ms / 10 ms; DC: 18 ms / 7 ms
> 2 x 105; 10 A. 250 V AC
see Fig. 2
> 2 x 105; 10 A. 250 V AC
see Fig. 2
> 2 x 105; 10 A. 250 V AC
see Fig. 2
> 2 x 107
> 2 x 107
> 2 x 107
35 x 35 x 54.4 mm
83 g
35 x 35 x 54.4 mm
83 g
35 x 42.5 x 54.5 mm
95 g
Ambient temperature
• storage
-40...+85 °C
-40...+85 °C
-40...+85 °C
• operating
AC: -40...+55 °C
DC: -40...+70 °C
AC: -40...+55 °C
DC: -40...+70 °C
AC: -40...+55 °C
DC: -40...+70 °C
Cover protection category
Environmental protection
Shock resistance
Vibration resistance
Solder bath temperature
Soldering time
IP 40 PN-EN 60529
RTI PN-EN 116000-3
10 g
5 g 10...150 Hz
max. 270 °C
max. 5 s
IP 40 PN-EN 60529
RTI PN-EN 116000-3
10 g
5 g 10...150 Hz
max. 270 °C
max. 5 s
IP 40 PN-EN 60529
RTI PN-EN 116000-3
10 g
5 g 10...150 Hz
max. 270 °C
max. 5 s
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
66