110 WATT SWITCHING POWER SUPPLIES
DESCRIPTION
(LVD)
RoHS
The PU110 series of compact, open PCB constructed,
AC-DC switching power supplies are capable of delivering
72 to 110 watts of continuous power at 25 CFM forced air
cooling or 52 to 80 watts at convection cooling. They
operate at 85 to 264VAC input voltage without the need of
a selector strap. They are ideally suited for use in small to
medium
size
digitally-based
systems,
such
as
point-of-sale equipment, microprocessor based systems,
and telecom equipment. All models meet the safety
requirements of UL, CSA and IEC.
FEATURES
‧ Recognized or certified by UL, CSA and TÜV
‧ Power Fail Detect (PFD) signal
‧ 100% burn-in
‧ Wide input range 85 to 264VAC
‧ Input surge current protection
‧ Overvoltage protection
Safety Standard Approvals:
‧ Overcurrent protection
‧ Compliant with RoHS requirements
UL 60950-1
INPUT SPECIFICATIONS
Input voltage:
Input frequency:
Input current:
85 to 264VAC
CSA C22.2 No. 60950-1
TÜV EN60950-1
47 to 63Hz
3.20A(rms)for 115VAC
1.80A(rms)for 230VAC
0.40mA max. @ 115VAC, 60Hz
0.75mA max. @ 230VAC, 50Hz
Earth leakage current:
(Touch current)
OUTPUT SPECIFICATIONS
Output voltage/current:
See rating chart
110 watts maximum at 25 CFM
forced air cooling or 80 watts
maximum at convection cooling
1﹪ peak to peak maximum
Provided on output #1 only; set at
112-132﹪ of its nominal output
voltage
GENERAL SPECIFICATIONS
Total output power:
Switching frequency:
20KHz to 250KHz, varies with load and
line
Ripple and noise:
Overvoltage protection:
Efficiency:
70﹪ minimum on single output models
with Vo≥12V, 65% minimum on the others
All outputs protected to short circuit
conditions
Overcurrent protection:
12 msec minimum at 110VAC
Hold-up time:
±0.5﹪ maximum at full load
Line regulation:
All outputs ±0.04﹪/ºC maximum
Temperature coefficient:
Transient response:
Maximum excursion of 4﹪ or
better on all models, recovering
to 1﹪ of final value within 500us
15 amps @ 115VAC or 30 amps
@ 230VAC, at 25ºC cold start
Inrush current:
Withstand voltage:
3000VAC from input to output
1500VAC from input to ground
500VAC from output to ground
after a 25﹪ step load change
TTL logic high for normal operation
and TTL logic low upon loss of
input power. This signal appears at
least 1ms prior to +5V output
dropping
5﹪ below its nominal value. This
signal also provides a minimum
delay of 100ms after +5V is within
regulation.
PFD signal:
400,000 hours minimum at full load
at 25ºC ambient, calculated per
MIL-HDBK-217F
MTBF:
EMC Performance (EN55024)
EN55022:
FCC:
VCCI:
Class B conducted, Class B radiated
Class B conducted, Class B radiated
Class B conducted, Class B radiated
Harmonic distortion, Class A
Line flicker
ESD, ± 8KV air and ± 4KV contact
Radiated immunity, 3V/m
EN61000-3-2:
EN61000-3-3:
EN61000-4-2:
EN61000-4-3:
ENVIRONMENTAL SPECIFICATIONS
Operating temperature:
Storage temperature:
0ºC to +70ºC
-40ºC to +85ºC
EN61000-4-4:
EN61000-4-5:
EN61000-4-6:
EN61000-4-8:
EN61000-4-11:
Fast transient/burst, ± 1KV
Surge, ± 1KV diff., ± 2KV com.
Conducted immunity, 3Vrms
Magnetic field immunity, 1A/m
Voltage dips, 30% reduction for
500ms and >95% reduction for 10ms
Relative humidity:
Derating:
5﹪ to 95﹪ non-condensing
Derate from 100﹪ at +50ºC
linearly to 50﹪ at +70ºC
110 watts continuous output power
at 25 CFM forced air cooling or
80 watts at convection cooling
Cooling: