Control Relays
Datasheet
PMP Series
• Single Phase Proportional Controller
• Output ratings up to 90 Amps at 600 VAC
Proportional Control SSRs
• Selectable operation mode: Phase Angle or Burst Fire control
• Selectable Control Input: 0-5 VDC, 0-10 VDC, 4-20 mA
• 50/60 Hz Adaptive Operational Frequency function
• 4-20 mA input does not require an auxiliary power supply
• LED multifunction status indicator
• Contactor configuration with "Elevator" screw terminals
• cURus, IEC Rated, CE & RoHS Compliant
The PMP Series of micro-controller based Single-Phase
method to be used can be selected on the unit by means of a
selector switch located on top of the SSR.
This selector switch also allows to select the type of analog signal
to be used at the control input. The available input types are: 0- 5
VDC, 0-10 VDC, and 4-20 mA.
PMP Series Proportional SSRs are ideal for lamp dimming and
resistive heating control, among other type of applications
requiring proportional control.
Proportional Control SSRs are designed to offer precise control of
the power delivered to a resistive load in a compact 22.5mm
housing, with ratings from 25 up to 90 Amps at 90 to 600 VAC.
PMP Series solid state relays can vary the output load power
proportionally to an analog control input from 0 to 100%. This can
be achieved by two different methods: Phase Angle control and
Burst Fire control (with Distributive Zero Cross). The control
PRODUCT SELECTION
Output Voltage
90-280 VAC
345-530 VAC
420-600 VAC
25 A
PMP2425W
PMP4825W
PMP6025W
50 A
PMP2450W
PMP4850W
PMP6050W
90 A
PMP2490W
PMP4890W
PMP6090W
AVAILABLE OPTIONS
Operating Voltage
Terminal Layout
W: Contactor Configuration
(elevator screw)
24: 90-280 VAC
48: 345-530 VAC
60: 420-600 VAC
Thermal Pad
Blank: Not Included
H: Included
Series
PMP
24
25
W
P
H
Rated Load Current
Overvoltage Protection (1)
Blank: Not Included
P: Included
25: 25 Amps
50: 50 Amps
90: 90 Amps
Required for valid part number
For options only and not required for valid part number
OUTPUT VOLTAGE SPECIFICATIONS(2)
Description
Operating Voltage (45-65Hz) [VRMS]
Transient Overvoltage [Vpk] (1)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec]
PMP24xxW
PMP48xxW
PMP60xxW
90-280
600
4
345-530
1200
2.2
420-600
1200
2
500
500
500
FDE-07-01 REV. A
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.