Protection Relays & Controls
Ground-Fault Protection – Ungrounded AC System
PGR-3200 SERIES
Insulation Monitor
Description
The PGR-3200 detects ground faults by continuously
monitoring the insulation integrity of ungrounded electrical
systems. The relay monitors the insulation for damage and
assists with predictive maintenance and troubleshooting of
developing ground faults by providing two warning and an
alarm level. The PGR-3200 operates on one- or three-phase
ungrounded systems up to 6 kV.
The PGR-3200 can also be used on a grounded system to
monitor the insulation for damage, while the power system
is de-energized. The mode-of-operation terminals (27-28)
are connected to the circuit breaker or contactor auxiliary
contacts to toggle the relay off when the contactor or
breaker is closed.
Features & Benefits
FEATURES
BENEFITS
Simplified Circuit Diagram
Meets National Electrical Code (NEC®) Article
250.21(B) and Canadian Electrical Code Part 1,
Section 10-106 (2) requirements for ungrounded
systems
NEC® and CEC Code
compliant
A
B
Form C output contact for alarming when the
insulation resistance is below 50 k
Output contact
(50 kΩ)
Ω
Form C output contact for tripping when the
insulation resistance is below 10 k
Output contact
(10 k
Ω)
Ω
C
Provides means for connecting to an optional
meter (PGA-0510) or control system
Analog output
(0-1 mA)
A
DIN-rail or surface
mount
Flexible options for ease of installation
Accessories
PGR-3200
(Insulation Monitor)
A
PGH Series High-Tension Coupler
A PGH Series high-tension coupler is
required for systems between 1,300 V and
6,000 V.
L1
L2
PGA-0510 Analog Ohm Meter
Optional PGA-0510 Analog Meter allows
for metering of insulation resistance.
Ordering Information
Specifications
IEEE Device Numbers
Undervoltage Relay (27)
Ground Detector Relay (64)
ORDERING NUMBER
CONTROL POWER
240 Vac(1)
PGR-3200
Input Voltage
See ordering information
H 75 mm (3”); W 100 mm (3.9”); D 115 mm (4.5”)
Dimensions
PGR-3200-120
120 Vac
Resistance Ratings
Insulation warning (30 kΩ and 50 kΩ)
Insulation alarm (10 k
Non-fail-safe
Local
Local and remote
Two Form C
Ω)
ACCESSORIES
PGH Series
PGA-0510
REQUIREMENT
Required >1,300 V
Optional
Contact Operating Mode
Test Button
Reset Button
Output Contacts
Analog Output
Conformally Coated
Approvals
0-1 mA
Note: For optional conformal coating please consult factory. To convert to a resistance
grounded system, see neutral-grounding-resistors packages.
Consult factory
UL Listed (E183688)
5 years
(1) UL Not Available
Warranty
Mounting
DIN, Surface
Rev: 4-A-041118
Based on Manual Rev: 3-E-040918
© 2018 Littelfuse Protection Relays & Controls