5秒后页面跳转
NSYCVF165M230PF PDF预览

NSYCVF165M230PF

更新时间: 2024-11-26 01:22:03
品牌 Logo 应用领域
其他 - ETC /
页数 文件大小 规格书
2页 64K
描述
ClimaSys forced vent. IP54, 165m3/h, 230V,with outlet grille and filter G2

NSYCVF165M230PF 数据手册

 浏览型号NSYCVF165M230PF的Datasheet PDF文件第2页 
Product data sheet  
Characteristics  
NSYCVF165M115PF  
ClimaSys forced vent. IP54, 165m3/h, 115V,  
with outlet grille and filter G2  
Main  
Range  
ClimaSys CV  
Fan  
Category  
Type of filter  
Flow rate  
Standard  
Free flow rate with standard filter : 193 m3/h at 60  
Hz  
Free flow rate with standard filter : 165 m3/h at 50  
Hz  
[Us] rated supply volt-  
age  
75...126 V  
Input voltage  
115 V 50/60 Hz  
Complementary  
Absorbed power  
14.4 W 60 Hz  
15.5 W 50 Hz  
[In] rated current  
0.18 A 60 Hz  
0.2 A 50 Hz  
Noise level < at  
Bearing type  
50...51 dB  
Ball  
Height  
External : 268 mm  
External : 248 mm  
External : 104 mm  
223 x 223 mm  
1.14 kg  
Width  
Depth  
Cut-out dimensions  
Product weight  
Material  
Injected thermoplastic (ASA PC) for outlet grille  
Colour  
Outlet grille : grey RAL 7035  
-20...60 °C  
Ambient air temperature for operation  
Ambient air temperature for storage  
Maximum pressure  
Connections - terminals  
IP degree of protection  
Device composition  
-40...70 °C  
50 Pa flow rate 0 m³/h  
Faston connector  
IP54  
1 power cord  
1 cut-out template  
1 outlet grille front  
1 filter front of axial motor  
2 protective grille on the front and rear surfaces  
1 axial motor  
Condition of use  
Outside temperature must be 5 °C lower than inside temperature  
Filter must be cleaned and replaced regularly  
Surrounding environment must be relatively clean  
Overfrequent filter replacement should be avoided  
Flow rates depends on the work point, see ProClima software  
Jun 16, 2015  
1

与NSYCVF165M230PF相关器件

型号 品牌 获取价格 描述 数据表
NSYCVF38M115PF ETC

获取价格

ClimaSys forced vent. IP54, 38m3/h, 115V,with outlet grille and filter G2
NSYCVF38M230PF ETC

获取价格

ClimaSys forced vent. IP54, 38m3/h, 230V,with outlet grille and filter G2
NSYCVF560M230PF ETC

获取价格

ClimaSys forced vent. IP54, 560m3/h, 230V,with outlet grille and filter G2
NSYCVF850M230PF ETC

获取价格

ClimaSys forced vent. IP54, 850m3/h, 230V,with outlet grille and filter G2
NSYPPA4G ETC

获取价格

Diagram Pocket
NSYPPA5G ETC

获取价格

Diagram Pocket
NSYTBP191610H SCHNEIDER

获取价格

PC box IP66 IK08 RAL7035 Int.H175W150D100 Ext.H193W164D105 opaque PC cover H40
NSYTBP19168 SCHNEIDER

获取价格

PC box IP66 IK08 RAL7035 Int.H175W150D80 Ext.H193W164D87 Opaque PC cover H20
NSYTBP241910 SCHNEIDER

获取价格

PC box IP66 IK08 RAL7035 Int.H225W175D100 Ext.H241W191D128 opaque PC cover H20
NSYTBP241912H SCHNEIDER

获取价格

PC box IP66 IK08 RAL7035 Int.H225W175D120 Ext.H241W194D127 opaque PC cover H40