描述
LIQUID LEVEL-CUTOFF 24VAC 2S

LLC6610F5P 数据手册

 浏览型号LLC6610F5P的Datasheet PDF文件第2页 
Protection Relays  
Pump Controls and Liquid Level Controls  
LLC6 SERIES  
Low Level Cutoff Liquid Level Controls  
Description  
The LLC6 Series is a plug-in, single-probe conductive liquid  
level control designed for low liquid level cutoff protection. It  
offers a factory fixed time delay of 1 - 60s and is available in  
input voltages of 24, 120, or 230VAC. LED indicator illuminates  
whenever the LLC6s 10A, SPDT output relay is energized.  
Available with automatic/manual reset or a special manual reset  
with power outage feature, which auto resets the unit when  
power is restored and the water level is acceptable. 24VAC and  
120VAC units are recognized as limit switches under UL353  
(230VAC units are UL508) and CSA certified under Standard 14.  
11-PIN  
Operation  
Automatic Reset (Reset terminals not connected): When  
liquid rises to the low level cutoff probe, the output relay and  
the LED indicator energize. When the liquid falls below low level  
cutoff probe, the output relay and the LED indicator de-energize  
after a fixed time delay.  
Manual Reset (Reset switch connected): When the liquid  
level falls below the low level probe, the output relay and LED  
de-energize after a fixed time delay. When the liquid level rises  
to the low level probe, the output relay and LED indicator remain  
de-energized until the manual reset switch is opened; then they  
energize immediately.  
Wiring Diagram  
PC = Probe  
Common  
P = Probe  
V = Voltage  
R = Optional NC  
Reset Switch  
Power Outage Manual Reset (Reset switch connected): A  
power outage causes the output relay and LED indicator to  
de-energize. Upon restoration of power, if the liquid level is  
above the low level probe, the output relay and LED indicator  
will re-energize. If the liquid level is below the low level probe,  
the output relay and LED indicator remain de-energized until the  
Normally Closed (NC) reset switch is opened.  
N/L2  
L1  
Connect common  
to conductive tank.  
Additional probe is  
necessary for  
Metal Tank or use  
additional Probe  
non-conductive or  
insulated tanks.  
Features & Benefits  
FEATURES  
BENEFITS  
Isolated 12VAC on probe Prevents electrolysis  
Industry standard 11-pin  
octal plug connection  
Eliminates need for special connectors  
LED indication  
Visual indication output relay is energized  
Power outage protection  
(see ordering table  
for models)  
Automatically resets the unit when power is  
restored and the water level is acceptable  
Ordering Information  
TIME DELAY  
(FIXED)  
SENSE  
RESISTANCE  
MODEL  
INPUT VOLTAGE  
RESET  
LLC6210F10M  
LLC6410F10M  
LLC643F26M  
LLC6610F5P  
24VAC  
10s  
10s  
3s  
10kΩ  
Manual/Automatic  
120VAC  
120VAC  
230VAC  
10kΩ  
Manual/Automatic  
26kΩ  
Manual/Automatic  
10s  
5kΩ  
Power Outage Manual Reset  
If you don’t find the part you need, call us for a custom product 800-843-8848  
© 2016 Littelfuse Protection Relays & Controls  
www.littelfuse.com/llc6  
Rev: 1-A-062716  

与LLC6610F5P相关器件

型号 品牌 描述 获取价格 数据表
LLC825F5M LITTELFUSE LLC825F5M is a low level, conductive liquid l

获取价格

LLC842F103M LITTELFUSE The LLC8 Series is a low cost, single-probe conductive liquid level control designed for l

获取价格

LLC8430F250P LITTELFUSE The LLC8 Series is a low cost, single-probe conductive liquid level control designed for l

获取价格

LLC8430F26P LITTELFUSE The LLC8 Series is a low cost, single-probe conductive liquid level control designed for l

获取价格

LLC843F10M LITTELFUSE The LLC8 Series is a low cost, single-probe conductive liquid level control designed for l

获取价格

LLC843F10P LITTELFUSE The LLC8 Series is a low cost, single-probe conductive liquid level control designed for l

获取价格