5秒后页面跳转
KCR PDF预览

KCR

更新时间: 2024-11-21 22:07:47
品牌 Logo 应用领域
其他 - ETC 限制器
页数 文件大小 规格书
5页 1169K
描述
BUSS CABLE LIMITER

KCR 数据手册

 浏览型号KCR的Datasheet PDF文件第2页浏览型号KCR的Datasheet PDF文件第3页浏览型号KCR的Datasheet PDF文件第4页浏览型号KCR的Datasheet PDF文件第5页 
Effective February 2019  
Supersedes October 2017  
Technical Data 1042  
250 V and 600 V cable limiters  
Features and benefits:  
Cable limiters enhance multi-conductor system  
reliability by isolating faulted conductors and  
taking them offline while the balance of the  
conductors continue delivering power to their  
circuits. This is why cable limiters are often  
used in utility low voltage networks and large  
multi-cable per phase service entrances.  
Cable limiters enhance service entrance  
conductor short-circuit protection with current-  
limiting performance that exceed the typical  
protection offered by utility overcurrent  
protective devices.  
Cable limiters meet many system requirements  
with 250 Vac or 600 Vac ratings for conductor  
sizes from 12 AWG to 1000 kcmil and terminal  
options available that make them easy to install  
including:  
Tube-to-tube (crimp)  
Tube-to-offset bolt (crimp/bolt-in)  
Tube-to-center bolt (crimp/bolt-in)  
Compression rod-to-tube (crimp)  
Bolt-to-offset bolt (bolt-in)  
Product description:  
Cable limiters are intended to provide short-circuit  
protection to electrical systems, typically between  
the transformer and service entrance. Should a  
short-circuit occur, the cable limiter removes the  
affected cable(s) from service and permits the  
other conductors to continue delivering power.  
Select cable limiters are UL Listed under File  
E90818 for use on 600 V circuit for protection  
against faults up to 200 kA.  
Cable limiters are often used in utility low voltage  
networks and large multi-cable per phase service  
entrances.  
Unlike fuses, cable limiters are selected by cable  
size rather than amp rating, e.g., a “4/0” limiter  
will carry the current of a 4/0 cable.  
Limiters are stable, totally self-contained, static  
devices with unchanging characteristics that  
operate without venting ionized gases or explosive  
action.  
Under high short-circuit conditions, limiters cut off  
fault currents within one-half cycle (0.008 second)  
and reduce insulation damage from the immense  
heat that is developed by sustained fault current  
flow. They confine damage to the point of the  
short-circuit and stop long-length cable burn-back  
and striking of multiple arcs. This minimizes or  
eliminates damage to adjacent conductors.  

与KCR相关器件

型号 品牌 获取价格 描述 数据表
KCR1206T KOA

获取价格

three-terminal capacitor/resistor
KCR1206T1 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T101/101 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T101/500 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T220/101 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T220/500 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T221/101 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T221/500 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T470/101 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines
KCR1206T470/500 KOA

获取价格

Three Termination Capacitor/Resistor EMI Filter for Signal Lines