HR series
HR 12120W 12V 120W
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
Design for Standby Power Applications
【Design Life】
【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Up to 5 Years in Standby Service at 25℃
Eurobat (20℃) : 3-5 years, Standard Commercial
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : -15℃ ~ 50℃ (5℉~122℉)
Charge: -15℃ ~ 40℃ (5℉~104℉)
Storage: -15℃ ~ 40℃ (5℉~104℉)
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored
at higher temperature than 25℃ (77℉).
Design according with IEC 61056-1/2:2012
12V (6 cells per unit)
Specification
Nominal Voltage
Nominal Capacity
120W @15min-rate to 1.67V per cell @25℃ (77℉)
Weight
Approx. 10.20 Kg (22.48 lbs)
Maximum Discharge Current
Internal Resistance
Short Circuit Current
Maximum Charge Current
Terminal types
225A (5sec)
Approx. 8.2 mΩ
928A
12A
I1 terminal to accept M5 bolt
Terminal hardware Torque
Container Material
59 Kgf-cm / 51 Ibf-in / 5.73 N-m
ABS (UL 94-HB) & Flame Retardant (94-V0) available upon request
6.54±0.08
4.92±0.06
6.89±0.08
6.89±0.08
Length (L)
166.0±2.0 mm
125.0±1.5 mm
175.0±2.0 mm
175.0±2.0 mm
inch
inch
inch
inch
Width (W)
Dimensions
Container Height (h)
Overall Height (H)
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
2MIN
169
153
146
132
117
100
4MIN
148
135
128
117
105
92.5
5MIN
135
6MIN
125
8MIN
107
10MIN
94.2
88.9
85.6
80.2
73.3
67.3
15MIN
70.5
67.0
65.3
62.0
58.3
54.3
20MIN
56.1
53.6
52.5
50.4
48.0
45.7
30MIN
41.2
39.7
39.2
37.8
36.0
34.6
45MIN
30.4
29.6
29.2
28.3
27.1
26.0
60MIN
24.5
24.0
23.7
23.1
22.2
21.2
90MIN
16.8
16.6
16.4
16.2
15.8
15.2
124
117
108
97.2
86.8
115
109
101
91.2
82.4
100
95.5
88.9
81.3
74.3
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
2MIN
1745
1608
1539
1412
1273
1100
4MIN
1622
1495
1427
1306
1181
1045
5MIN
1507
1393
1333
1224
1113
1001
6MIN
1419
1315
1260
1161
1060
966
8MIN
1199
1119
1084
1012
944
10MIN
1030
975
15MIN
771
20MIN
621
30MIN
462
45MIN
348
341
337
329
319
307
60MIN
284
279
276
270
263
253
90MIN
197
194
193
190
186
181
738
724
701
676
600
590
578
561
453
447
435
418
947
895
853
805
877
648
536
402
Please refer to the official site for the lastest rating confirmation. URL: www.csb-battery.com
Issued:
161101
Sales Offices
Recognized under UL 1989,
and certified by ISO 9001, 14001.
BUSINESS HEADQUARTERS
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
USA OFFICE
EUROPE (EMEA) OFFICE
Tel: +31(0)180-418-140
Fax: +31(0)180-418-327
TAIPEI OFFICE
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)
Fax: +1-817-244-4445
SHENZHEN OFFICE (CHINA)
Tel: +86-755-8831-6488, 8831-6775
Fax: +86-755-8831-6075
SHANGHAI OFFICE (CHINA)
Tel: +86-21-5046-1622, 5046-0833
Fax: +86-21-5046-1046
BEIJING OFFICE (CHINA)
Tel: +86-10-5820-5336, 5820-5338
Fax: +86-10-5820-3053