150/180 Watts
GCS Series
xppower.com
•
•
•
•
•
•
•
Convection/Forcedꢀcooled Ratings
IT & Medical Safey Approvals (Class I & II)
< 0.5W Standby Power
ꢀ40° C to +70° C Operation
Remote On/Off (ꢀR Models)
Class B Emissions
3 Year Warranty
Specification
Input
General
Efficiency
Isolation
• 93% typical
Input Voltage
• 85-264 VAC, derate output power
<90 VAC by 10%
• 47-63 Hz
• 1.5/1.8 A typical at 115 VAC, full load
(150/180 W)
• 4000 VAC Input to Output 2 x MOPP,
1500 VAC Input to Ground 1 x MOPP,
500 VDC Output to Ground
Input Frequency
Input Current
Switching Frequency
MTBF
Power Density
• 65/100 KHz PFC/Main Converter
0.7/0.8 A typical at 230 VAC, full load
(150/180 W)
• 569 kHrs to MIL-HDBK-217F at 25 °C, GB
3
• 8.5 W/in
Inrush Current
• 80 A typical at 230 VAC, cold start at 25 °C
Power Factor
• EN61000-3-2, class A Compliant
(Class C > 50 W load)
Environmental
Operating Temperature • -40 ˚C to +70 ˚C derate linearly from +50
Earth Leakage Current • 200 µA max at 264 VAC/60 Hz
No Load Input Power • <0.5 W
Input Protection
°C at 2.5%/˚C to 50% load at +70 °C
• Convection & Fan cooled ratings (see
Models & Ratings tables)
Cooling
• Internal T3.15 A/250 V fuse in line
and neutral
Operating Humidity
• 95% RH, non-condensing
Output
Storage Temperature • -40 °C to +85 °C
Operating Altitude
Shock
• 3048 m
3 x 30g shocks in each plane, total 18
shocks. 30g = 11ms (+/-0.5msec), half
sine, conforms to EN60068-2-27 &
EN60068-2-47
• Single axis 10 - 500 Hz at 2g sweep and
endurance at resonance in all 3 planes.
Conforms to EN60068-2-6
Output Voltage
• 12-48 VDC (see Models & Ratings table)
•
Output Voltage Trim
•
2%, fan output will track by
same percentage
Initial Set Accuracy
Minimum Load
Start Up Delay
Hold Up Time
Drift
•
1% V1, 5% V Fan
• None
• 0.5 s max
• 18 ms typical
Vibration
•
•
•
0.2% after 20 min warm up
0.5% max
0.5% V1, 5% V Fan
EMC & Safety
Low Voltage PSU EMC • EN61204-3, high severity level
Emissions
Line Regulation
Load Regulation
Over/Undershoot
• 12 - 28 V models none,
48 V models typically 5%
• 4% max. deviation, recovery to within
1% in 500 µs for a 50-75-50% load
change
• EN55011/22 level B conducted
EN55011/22 level B radiated (GCS180
level A)
• EN61000-3-2, class A & C
• EN61000-3-3
• EN61000-4-3, level 3 Perf Criteria A
• EN61000-4-4, level 3 Perf Criteria A
Transient Response
Ripple & Noise
Harmonic Currents
Voltage Flicker
Radiated Immunity
EFT/Burst
• 1% pk-pk V1, 12 V models 1.5%,
20 MHz bandwidth
Overvoltage Protection • 115-140% Vnom, recycle input to reset
Overload Protection • 110-150% V1 only
Short Circuit Protection • Continuous
Surge
• EN61000-4-5, installation class 3
Perf Criteria A
• EN61000-4-6, level 3 Perf Criteria A
• EN55024 & EN60601-1-2 (see longform
datasheet for details)
Conducted Immunity
Dips & Interruptions
Temperature
Coefficient
• 0.05%/˚C
Safety Approvals
• EN60601-1, ANSI/AAMI ES60601-1,
CSA22.2 No. 60601-1 per cUL, Including
Risk Management, EN60950, UL60950
Remote Sense
Remote On/Off
• Compensates for 0.5 V total voltage drop
• Optional, -R models (see longform
datasheet for full details)