FXC6000 AC-DC Series Data Sheet
Features
• Three-phase AC input
• Suitable for 3U or 5U height mounting
• Single-wire current share or droop current share
• Remote voltage adjust and current monitoring
• Overtemperature, overload, and overvoltage protection
• LED supply status indicators
• Current share control for up to 30 units
• Front panel selectable-input-range
FXC6000
Front & Rear Views
Description
The FXC6000 Series of standalone or rack-mounted
power systems provides true AC front-end capability to
automatic test equipment, telecom, data commun-
ications, and other distributed power designs. The FXC
systems may be paralleled up to 180 kW of output power
and is intended for chassis-mounted installations with
bolted connections. These power supplies provide
excellent protection against input voltage transients.
the rear. Alarm, monitoring, and control signals are
floating from the main output and can be referenced to
the positive or negative output or sense line of the power
supply. The output is floating with respect to the chassis
and may be used as a positive or negative polarity
supply.
The FXC6000 Series meets international safety
requirements and is CE Marked to the Low Voltage
Directive. This series operates on three-phase European
voltages as well as (up to) 480VAC, D or Y.
The FXC has its fan located at the front of the supply, and
voltage adjust, indicator lights, output bussbars, and
connectors on the rear. Airflow is from the front through
Chassis-Mountable Model
OUTPUT
VOLTAGE
INPUT VOLTAGE RANGE
3-PHASE (VAC)
ADJUSTMENT
RANGE
MAXIMUM OUTPUT
CURRENT
LINE
REGULATION
LOAD
INITIAL SETTING
ACCURACY
MODEL
REGULATION (NOTE 1)
FXC6000-48-S (NOTE 2) 48V
180 to 264 or 342 to 528
45.6V to 50.4V
125A
0.15%
0.2%
47.90V to 48.10V
NOTES: 1) With Remote Sense connected.
2) User-selectable input voltage ranges.
Input Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
Input Voltage - AC
3-phase delta low input range, nominal.
3-phase delta high input range, nominal.
Continuous deviation from the above nominals.
200
380
-10
240
480
+10
%
Input Current
Inrush Surge Current
Per phase at full rated load.
Internally limited.
FXC6000 at 180 VAC:
Vin = 264VAC (one cycle). 25° C:
Vin = 528VAC (one cycle). 25° C:
28
38
38
ARMS
APK
Input Frequency
Hold-up Time
AC input.
After last AC line peak at full power.
50
20
20
60
Hz
208 VAC:
415 VAC:
ms
Operating Frequency
Power Factor
Switching frequency, fixed.
100
kHz
W/VA
0.90
AUG 25, 2004 revised to JAN 09, 2007
Page 1 of 4