5秒后页面跳转
FCA-50-R/Q PDF预览

FCA-50-R/Q

更新时间: 2024-11-22 02:40:07
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
3页 104K
描述
Space-saving Plug-in Signal Conditioners F-UNIT

FCA-50-R/Q 数据手册

 浏览型号FCA-50-R/Q的Datasheet PDF文件第2页浏览型号FCA-50-R/Q的Datasheet PDF文件第3页 
MODEL: FCA  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
Space-saving Plug-in Signal Conditioners F-UNIT  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
CT TRANSMITTER  
(Average sensing, RMS calibrated)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
Functions & Features  
• Converting an alternating current from a current  
transformer into a standard process signal  
• Minimum ripple  
• Average sensing  
• CT Protector provided for open-circuit protection  
• Highdensity mounting  
[3] POWER INPUT  
Typical Applications  
AC Power  
• Centralized monitoring and control of motors, pumps or  
heaters by DCS  
K: 85 – 132 V AC  
(Operational voltage range 85 – 132 V, 47 – 66 Hz)  
L: 170 – 264 V AC  
• Monitoring power line and power supply current  
(Operational voltage range 170 – 264 V, 47 – 66 Hz)  
DC Power  
26 (1.02)  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
P: 110 V DC  
100  
(3.94)  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
[4] OPTIONS  
blank: none  
137  
(5.39)  
mm (inch)  
/Q: With options (specify the specification)  
MODEL: FCA–[1][2]–[3][4]  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
ORDERING INFORMATION  
• Code number: FCA-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. FCA-1A-K/Q)  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
[1] INPUT (sine wave)  
Current  
1: 0 – 1 A AC  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Input waveform  
5: 0 – 5 A AC  
[2] OUTPUT  
Average sensing: Sine wave  
Current  
Overrange output: 0 to 120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
FCA SPECIFICATIONS  
ES-1437 Rev.7 Page 1/3  
http://www.m-system.co.jp/  

与FCA-50-R/Q相关器件

型号 品牌 获取价格 描述 数据表
FCA-51-K MSYSTEM

获取价格

Space-saving Plug-in Signal Conditioners F-UNIT
FCA-51-K/Q MSYSTEM

获取价格

Space-saving Plug-in Signal Conditioners F-UNIT
FCA-51-L MSYSTEM

获取价格

Space-saving Plug-in Signal Conditioners F-UNIT
FCA-51-L/Q MSYSTEM

获取价格

Space-saving Plug-in Signal Conditioners F-UNIT
FCA-51-P MSYSTEM

获取价格

Space-saving Plug-in Signal Conditioners F-UNIT
FCA-51-P/Q MSYSTEM

获取价格

Space-saving Plug-in Signal Conditioners F-UNIT
FCA-51-R MSYSTEM