AC-DC Power Supplies

DNR120AS24 数据手册

 浏览型号DNR120AS24的Datasheet PDF文件第2页浏览型号DNR120AS24的Datasheet PDF文件第3页浏览型号DNR120AS24的Datasheet PDF文件第4页 
120-480 Watts  
xppower.com  
DNR120-480 Series  
Up to 90% Efficiency  
Wide Adjustment Range  
Three-phase 480 W Versions  
Parallel Function  
DC Standby Versions  
Full Power to +60 °C  
Connector Options  
Specification  
Input  
General  
Input Voltage  
• DNR120LS: 93-132/186-264 VAC  
switch select, 210-370 VDC switch in  
230 VAC position  
DNR120AS: 90-132/186-264 VAC  
auto select, 210-370 VDC  
DNR240PS: 93-132/186-264 VAC,  
auto select, 210-370 VDC  
DNR480PS: 90-264 VAC, 120-370 VDC  
DNR480TS: 340-575 VAC 3Ø, 480-820VDC  
Efficiency  
Isolation  
• See tables  
• 3000 VAC Input to Output  
1500 VAC Input to Ground  
500 VAC Output to Ground  
Switching Frequency  
Signals  
• 100 KHz typical  
• DC ON indicator LED Green,  
DC LOW indicator LED Red  
DC OK: 24 V models  
MTBF  
• 200 kHrs typical per MIL-HDBK-217F  
GF, +40 °C  
Input Frequency  
Inrush Current  
• 47-63 Hz  
• 120 W: 24/48 A at 115/230 VAC  
240 W: 30/60 A at 115/230 VAC  
480PS: 25/50 A at 115/230 VAC  
480TS: 33 A at 575 VAC  
Environmental  
Operating Temperature • DNR120-240: -10 °C to +70 °C, derate  
linearly from +60 °C at 2.5%/°C  
Power Factor  
• Meets EN61000-3-2 for class A equipment  
DNR480 PS: -25 °C to +70 °C, derate  
linearly from +55 °C at 2.5%/°C  
Earth Leakage Current • 0.8 mA max  
DNR480 TS: -25 °C to +70 °C, derate  
linearly from +60 °C at 2.5%/°C.  
Output  
Output Voltage  
• See tables  
• See tables  
ꢀsee derating curvesꢁ  
Output Voltage Trim  
Initial Set Accuracy  
Minimum Load  
Cooling  
• Convection-cooled  
1%  
Operating Humidity  
Storage Temperature  
Shock  
• 20-95% RH, non-condensing  
• -25 °C to +85 °C  
• No minimum load required  
• <1000 ms  
Start Up Delay  
• 4 g, 22 ms, X, Y & Z axis  
• 1 g, 10 Hz to 500 kHz, along X, Y & Z axis  
Start Up Rise Time  
Hold Up Time  
• <150 ms  
Vibration  
• 120 & 240 W: 25/30 ms at 115/230 VAC  
480PS: 30 ms at 115/230 VAC  
480TS: 20 ms at 340 VAC  
EMC & Safety  
Emissions  
• EN55022, class B conducted & radiated  
• EN61000-3-2, class A  
Line Regulation  
Load Regulation  
0.5% max ꢀ 1% max for 480TSꢁ  
Harmonic Currents  
Voltage Flicker  
ESD Immunity  
Radiated Immunity  
EFT/Burst  
1% ꢀ 5% for units in parallelꢁ,  
120LS models - see note 1  
• EN61000-3-3  
• EN61000-4-2, level 3 Perf Criteria A  
• EN61000-4-3, level 3 Perf Criteria A  
• EN61000-4-4, level 3 Perf Criteria A  
• EN61000-4-5, level 3 Perf Criteria A  
• EN61000-4-6, level 3 Perf Criteria A  
Transient Response  
Ripple & Noise  
• 300 µs for a 50% load change  
• 120 W models: 50 mV pk-pk  
240-480 W models: 100 mV pk-pk.  
20 MHz BW  
Surge  
Conducted Immunity  
Dips & Interruptions  
Overvoltage Protection • Output clamps at 125-145% Vnom  
• EN61000-4-11, 30% 10 ms,  
60% 100 ms, 100% 5000 ms  
Perf Criteria A, B, B  
Overload Protection  
• 105-145% constant current.  
480TS model: 115-135% continuous  
power limit, Imax = 2 x Inom at short  
circuit condition or switchable trip and  
restart mode, output is turned on for 3 s  
every 30 s.  
Safety Approvals  
• EN60950-1:2001, UL508, UL60950-1,  
cUL60950-1, CE Mark  
Temperature  
Coefficient  
0.02%/°C  

与DNR120AS24相关器件

型号 品牌 获取价格 描述 数据表
DNR120AS24-I XPPOWER

获取价格

AC-DC Power Supplies
DNR120AS48 XPPOWER

获取价格

AC-DC Power Supplies
DNR120AS48-I XPPOWER

获取价格

AC-DC Power Supplies
DNR120LS12 XPPOWER

获取价格

AC-DC Power Supplies
DNR120LS24 XPPOWER

获取价格

AC-DC Power Supplies
DNR120LS48 XPPOWER

获取价格

AC-DC Power Supplies
DNR120TS12 XPPOWER

获取价格

AC-DC Power Supplies
DNR120TS24 XPPOWER

获取价格

AC-DC Power Supplies
DNR18US05 XPPOWER

获取价格

AC-DC Power Supplies
DNR18US05-S XPPOWER

获取价格

AC-DC Regulated Power Supply Module, 18W