5秒后页面跳转
DNR PDF预览

DNR

更新时间: 2024-09-30 06:54:15
品牌 Logo 应用领域
SYSTEMSENSOR 光电
页数 文件大小 规格书
4页 1295K
描述
Intelligent Non-Relay Photoelectric Duct Smoke Detector

DNR 数据手册

 浏览型号DNR的Datasheet PDF文件第2页浏览型号DNR的Datasheet PDF文件第3页浏览型号DNR的Datasheet PDF文件第4页 
Intelligent Non-Relay  
Photoelectric Duct  
Smoke Detector  
The InnovairFlexSeries are the only duct smoke  
detectors flexible enough to fit configurations from  
square to rectangular and everything in between.  
The InnovairFlex DNR intelligent non-relay photoelectric duct  
smoke detector and DNRW watertight non-relay photoelectric duct  
smoke detector feature a pivoting housing that fits both square and  
rectangular footprints capable of mounting to a round or  
rectangular duct.  
Features  
• Photoelectric, integrated low-flow technology  
• Air velocity rating from 100 ft/min to 4000ft/min (0.5m/s to 20.32m/sec)  
• Versatile mounting options: square or rectangular configuration  
• Broad ranges for operating temperature (-4F to 158F) and humidity  
(0% to 95% non-condensing)  
DNRW duct smoke detector, with its NEMA 4 rating, is listed as a  
watertight enclosure providing protection against falling dirt, rain,  
and windblown dust, splashing and hose directed water, allowing  
operators to use the detector in the most extreme environments.  
• Patented sampling tube installs from front or back of the detector  
with no tools required  
• New Cover tamper signal  
These units sense smoke in the most challenging conditions,  
operating in airflow speeds of 100 to 4000 feet per minute,  
temperatures of -4F to 158F, and a humidity range of 0 to 95 percent  
(non-condensing).  
• Increased wiring space with a newly added 3/4-inch conduit  
knockout  
• Available space within housing to accommodate mounting of relay  
module  
An improved cover design isolates the sensor head from the low-  
flow feature for simple maintenance. A cover tamper feature was  
added to indicate a trouble signal for a removed or improperly  
installed sensor cover. The InnovairFlex housing provides a 3/4-inch  
conduit knockout and ample space to facilitate easy wiring and  
mounting of relay module.  
• Easily accessible code wheels on sensor head (sold separately)  
• Clear cover for convenient visual inspection  
• UL 268A listed  
• Remote testing capability  
• Requires com line power only  
• NEMA Type 4 UL listed for non-hazardous indoor and outdoor  
applications (DNRW only)  
The InnovairFlex duct smoke detector can be customized to meet  
local codes and specifications without additional wiring. The new  
InnovairFlex product line is compatible with all previous Innovair  
models, including remote test accessories.  
• UV Resistant, UL listed housing and cover material  
(DNRW only)  
WARNING: Duct smoke detectors have specific limitations.  
DUCT SMOKE DETECTORS ARE:  
Agency Listings  
NOT a substitute for an open area smoke detector,  
NOT a substitute for early warning detection, and  
NOT a replacement for a building’s regular fire detection system.  
Refer to NFPA 72 and 90A for additional duct smoke detector  
application information.  
2911  

与DNR相关器件

型号 品牌 获取价格 描述 数据表
DNR05US05 XPPOWER

获取价格

AC-DC Power Supplies
DNR05US05-S XPPOWER

获取价格

AC-DC Regulated Power Supply Module, 5W
DNR05US12 XPPOWER

获取价格

AC-DC Power Supplies
DNR05US12-S XPPOWER

获取价格

AC-DC Regulated Power Supply Module, 5W
DNR05US15 XPPOWER

获取价格

AC-DC Power Supplies
DNR05US24 XPPOWER

获取价格

AC-DC Power Supplies
DNR10US05 XPPOWER

获取价格

AC-DC Power Supplies
DNR10US05-S XPPOWER

获取价格

AC-DC Regulated Power Supply Module, 10W,
DNR10US12 XPPOWER

获取价格

AC-DC Power Supplies
DNR10US12-S XPPOWER

获取价格

AC-DC Regulated Power Supply Module, 10W