5ꢀ60 Watts
DNR Series
xppower.com
•
•
•
•
•
•
•
Rugged Design for Industrial Applications
Up to 89% Efficiency
Full Power to +60 °C
Wide Adjustment Range
DC OK 24 V Models
DC Standby Versions
3 Year Warranty
Specification
Input
General
Input Voltage
• 90-264 VAC, 120-375 VDC (DNR05/10/18)
Efficiency
Isolation
• See tables
• 3000 VAC Input to Output, 1500 VAC Input
to Ground, 500 VAC Output to Ground
85-264 VAC, 90-375 VDC (DNR30/60)
• 47-63 Hz
Input Frequency
Input Current
Inrush Current
• See tables
Switching Frequency
Signals
• 132 KHz typical, 55-90 kHz (DNR60)
• 5-18 W: 10/18 A at 115/230 VAC
30 W: 20/40 A at 115/230 VAC
60 W: 30/60 A at 115/230 VAC
• DC ON indicator LED Green: All models
DC LOW indicator LED Red: 5-18 W models
DC OK: 24 V 30-60 W models
DC OK: All standby models
Power Factor
Earth Leakage Current • 0.8 mA max
Input Protection
• EN61000-3-2, class A
MTBF
• 800 kHrs typical Bellcore, Issue 6 at +40 °C,
GB (DNR05/10/18), 530 kHrs typical
• Internal fuse T2A, 250 VAC fitted in line
Bellcore, Issue 6 at +40 °C, GB (DNR30/60)
DIN Rail
• Compatible with TS35/7.5 or TS35/15
Output
Output Voltage
• See tables
• See tables
Environmental
Operating Temperature • -20 °C to +70 °C (DNR05/10/18)
Output Voltage Trim
Initial Set Accuracy
Minimum Load
•
1ꢀ
-40 °C to +70 °C, start up at -35 °C
• No minimum load required
• <1 s (may increase at low
temperature extremes)
(DNR30/60), all units derate linearly from
60 °C (see derating curves)
Start Up Delay
Cooling
• Convection-cooled with 25mm free space
all sides
• 20-95ꢀ RH, non-condensing
Start Up Rise Time
Hold Up Time
• <150 ms
• 30/130 ms at 115/230 VAC (DNR05)
25/100 ms at 115/230 VAC (DNR10)
20/75 ms at 115/230 VAC (DNR18)
20/30 ms at 115/230 VAC (DNR30)
20/30 ms at 115/230 VAC DNR60)
• 5-18 W: 1.0ꢀ max
30-60 W: 0.5ꢀ max
• 5-18 W: 2.0ꢀ max
30-60 W: 0.5ꢀ max
• Redundancy module DPM10 available
for load currents up to 10 A (not with
standby system), contact sales
• 4ꢀ max deviation recovery to within
1ꢀ in 2 ms for a 50ꢀ load change
Operating Humidity
Storage Temperature • -25 °C to +85 °C (DNR05/10/18)
-40 °C to +85 °C (DNR30/60)
• 15 g, 11 ms, X, Y & Z axis, 3 shocks/axis
in both directions
• 2 g, 10 Hz to 500 Hz, along X, Y & Z axis,
60 mins/axis, mounted on rail
Shock
Line Regulation
Load Regulation
Parallel Operation
Vibration
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
• EN55022, level B conducted & radiated
• EN61000-3-2, class A
• EN61000-3-3
• EN61000-4-2, level 4, Perf Criteria A
• EN61000-4-3, level 3, Perf Criteria A
• EN61000-4-4, level 4, Perf Criteria A
Transient Response
Ripple & Noise
• 50 mV pk-pk, 20 MHz bandwidth (may
increase at low temperature extremes)
Overvoltage Protection • Output clamps at 120-145ꢀ Vnom,
auto recovery
• 110-145ꢀ constant current (DNR05-18)
105-150ꢀ power limited (DNR30/60)
Surge
• EN61000-4-5, installation class 3,
Perf Criteria A
Overload Protection
Conducted Immunity
Magnetic Field
Dips & Interruptions
• EN61000-4-6, level 3, Perf Criteria A
• EN61000-4-8, level 4 Perf Criteria A
• EN61000-4-11, 30ꢀ 10 ms,
60ꢀ 100 ms, 100ꢀ 5000 ms
Perf Criteria A, B, B
Short Circuit Protection • Power limited, auto recovery
Temperature
Coefficient
•
0.03ꢀ/°C
Safety Approvals
• EN60950-1, UL508 Pollution Degree 2,
UL1310 class 2 power recognised,
See note 3 & ratings table,
UL60950-1 Overvoltage Category II,
UL508 Overvoltage Category III,
DNR30 & DNR60: SEMI F47
ANSI/ISA 12.12.01. Class 1, Division 2
Groups A,B,C and D