MODEL: DA3
Plug-in Signal Conditioners M-UNIT
[3] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
D/A CONVERTER
(16-bit resolution)
47 – 66 Hz)
DC Power
Functions & Features
R3: 12 – 24 V DC
• Converts parallel digital signal into a DC output
• BCD, binary, offset binary, two's complement, reflected
binary inputs
(Operational voltage range 10.8 - 26.4 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
• Positive or negative logic selectable
• Display can be scaled in convenient engineering unit
• Scalable DC output range
[4] OPTIONS (multiple selections)
• Parity check
Input
Blank: TTL level
Typical Applications
/A: 24 V DC
• Interface of analog signal for computers and PLC
Other Options
blank: none
/Q: Option other than the above (specify the specification)
50
(1.97)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
80
(3.15)
/C02: Polyurethane coating
/C03: Rubber coating
139
(5.47)
TERMINAL SCREW MATERIAL
/S01: Stainless steel
mm (inch)
MODEL: DA3–[1][2]–[3][4]
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable (model: MCN26)
ORDERING INFORMATION
• Code number: DA3-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. DA3-V11-M2/A/Q)
GENERAL SPECIFICATIONS
Construction: Plug-in
• Specify the specification for option code /Q
(e.g. /C01/S01)
Connection
Input: 26-pin connector(OMRON XG4A-2634)
Paired connector: OMRON XG4M-2630-T, XG5M-263x-N
Cover: OMRON XG5S-2612
Use Ordering Information Sheet (No. ESU-1395) for
specifying programmable variables. Default setting will be
used if not specified.
Output, power: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
[1] OUTPUT
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -15 to +115 %
■DISPLAY
Current
Z1: Range 0 – 20 mA DC (Load resistance 600Ω max.)
Voltage
V1: Range -1 – +1 V DC (Load resistance 1000Ω min.)
V2: Range -10 – +10 V DC (Load resistance 10kΩ min.)
LED: 7 mm (.28") 7 segment, red
Number of display digits: 4 digits for DATA display; 2 digits
for ITEM display
[2] RESPONSE TIME
1: 400 msec.
PV indication: Input signal in engineering unit
Overrange indication: LEDs blinking
Power saving mode: Displays turn off if the keys are
untouched for a preset time period
2: 10 msec.
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 1/7
https://www.m-system.co.jp/