General Specifications  
Model  
Unit classification  
Compatible Racks  
CJ-series Basic I/O Unit  
CJ-series CPU Rack or  
CJ1W-TS562  
CJ-series Expansion Rack  
Max. number of  
Units  
10 Units/Rack max.  
RTD input unit  
(This requires a CJ1G or CJ1H CPU)  
Basic I/O area CIO0000 – 0999  
(3, 4 or 6 words allocated in IO Table)  
CPU Unit data area  
for inputs  
Insulation resistance  
20 Mmin. (at 500 V DC) between  
input terminals and external AC  
terminals (Power Supply Unit)  
500 VAC 50/60 Hz for 1 min. (detection  
current: 1 mA),  
INSTRUCTION SHEET  
Dielectric Strength  
Thank you for purchasing an OMRON product. Read this  
instruction sheet thoroughly and familiarise yourself with the  
functions and characteristics of the product before using it.  
To ensure safe and correct use of this Unit, also read the  
Operation- and Programming Manuals for your CJ1 PLC system.  
between Input terminals and external  
AC terminals (Power Supply Unit)  
250 mA max., 5 V DC,  
Internal current  
consumption  
Dimensions  
Weight  
from the CJ1 I/O bus.  
31 x 90 x 65 mm (W x H x D)  
150 g max.  
Other general specifications conform to  
the CJ-series general specifications.  
See Operation Manual W393.  
Keep this instruction sheet for future reference.  
Other  
OMRON MANUFACTURING OF THE NETHERLANDS B.V.  
OMRON Corporation 2004  
All Rights Reserved  
Unit Description  
Characteristics  
The CJ1W-TS562 is a 6-channel input unit for Pt100 and Pt1000  
RTD’s. It can be installed in any CJ1-series PLC system.  
It is classified as a basic I/O unit, occupying 48, 64 or 96 I/O points,  
depending on the number of activated inputs.  
Temperature Sensor  
Number of inputs  
Pt100 or Pt1000 (IEC 60751)  
1 to 6  
Measurement range  
Pt100:  
-200.0 to +650.0 °C  
Pt1000: -200.0 to +650.0 °C  
0.1 °C  
Always verify that the maximum I/O capacity of the CJ1 CPU is  
sufficient for the number of required I/O points.  
Indication resolution  
Leadwire  
Automatic, measured on B’ terminals,  
updates one sensor in each scan cycle.  
16-bit signed integer in units of 0.1 °C:  
#F830 = -200.0 °C, #1964 = +650.0 °C  
± 0.5 % of indicated value or ± 0.8 °C  
(whichever is larger) ± 1 digit max.  
when using 3-wire connection.  
compensation  
Temperature value  
Data representation  
Indication accuracy  
over full operational  
range (0 – 55 °C  
ambient temperature)  
Input response time  
(per active input)  
Nomenclature  
Unit status indicators  
RUN  
ERC  
(green)  
(red)  
40 ms (100 Hz suppression)  
67 ms (60 Hz suppression)  
80 ms (50 Hz suppression)  
400 ms (50+60 Hz suppression)  
[number of active inputs + 1] x [input  
response time] + 40 ms  
Sensor error indicators  
1 - 6 (red)  
Input update cycle  
time (all active inputs)  
I/O refresh time  
(influence on PLC  
cycle time)  
Removable Terminal Block  
Connections for  
1-3 inputs (48pt mode): 0.008 ms  
RTDs 1 through 6  
4
inputs (64pt mode): 0.011 ms  
5-6 inputs (96pt mode): 0.016 ms  
DIP switches  
(remove terminal block for access)  
Select input types (Pt100/Pt1000)  
Select filter functions  
LED indicators  
Select number of active inputs (1-6)  
Name  
State Description  
Terminal Block latch  
RUN  
OFF  
Fatal error or no power supply.  
Slide down to remove  
Slide up to lock  
(Green)  
Check the host PLC’s CPU status, and the  
status of other I/O units. If all other units  
function normally, replace the Unit  
Unit functions normally.  
ON  
Wiring  
ERC  
No fatal errors.  
OFF  
ON  
(Red)  
Incorrect DIP switch setting  
Use the same length and type of leadwire for each RTD’s  
Fatal error in the Unit.  
terminals A, B, and B’, so that the leadwire impedances will be  
the same. 2-wire connection can be used by shorting B-B’, but  
the specified indication accuracy cannot be guaranteed.  
Check the CPU unit for error codes.  
Re-start the PLC system.  
If the ERC LED is still lit, replace the unit.  
Measurement of the corresponding channel is  
within range, or  
For activated but unused inputs, short-circuit the A–B and B–B’  
terminals, to prevent unstable readout on the other inputs.  
Sensor  
Error  
OFF  
1 – 6  
Channel has been deactivated by DIP switch  
Keep the input wiring away from power lines including AC power  
supply lines and high-power lines. Do not run the I/O lines in the  
same duct or conduit as power lines.  
(Red)  
settings  
ON  
Measured temperature out-of-range, or  
RTD broken wire or short circuit  
The input circuits are galvanically isolated from the PLC’s I/O bus,  
but there is no galvanic isolation between individual inputs. All B’  
terminals are interconnected in the unit.  
All ON Calibration data not found or incorrect. The Unit  
should be returned to OMRON for calibration.  
Always ground the  
terminal on the Power Supply Unit of the  
PLC. In case of shielded sensor wiring, connect the shields to the  
same grounding point as the PLC.  

与CJ1W-TS562相关器件

型号 品牌 获取价格 描述 数据表
CJ1W-V600C11 OMRON

获取价格

Reference Information
CJ1W-V600C12 OMRON

获取价格

Reference Information
CJ201003DB AAC

获取价格

Thick Film Chip Resistors
CJ201003DK AAC

获取价格

Thick Film Chip Resistors
CJ201003DM AAC

获取价格

Thick Film Chip Resistors
CJ201003DO AAC

获取价格

Thick Film Chip Resistors
CJ201003FB AAC

获取价格

Thick Film Chip Resistors
CJ201003FK AAC

获取价格

Thick Film Chip Resistors
CJ201003FM AAC

获取价格

Thick Film Chip Resistors
CJ201003FO AAC

获取价格

Thick Film Chip Resistors