Power Entry Modules with Line Filter
CD
www.schurter.com /PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole (5x20 mm or 6.3x32 mm), Line Switch 1- or
2-pole, Voltage Selector (Step)
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount :
Characteristics
- All single elements are already wired
- The fuse drawer "Fingergrip" can be removed by hand
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Screw-on mounting from front side
- 5 Functions :
Appliance Inlet , Line Switch , Fuseholder with interchangeable fuse
drawer for Fuse-links 5x20 mm or 6.3x32 mm , with or without voltage
selector (step switch) , Line filter in standard and medical version
- Quick connect terminals 4.8 x 0.8 mm
References
Alternative: version without line filter KD
Alternative: Standard version
Unique Selling Proposition
- Multifunctional Power Entry Module
- Solid metal flange
- Various fuse drawers
- Slim design
Weblinks
pdf-datasheet, html-datasheet, General Product Information, RoHS,
CHINA-RoHS, REACH, Distributor-Stock-Check, Accessories, Detailed
request for product
Approvals
- VDE Certificate Number: 40004665 (FKSO, FKSP, FKSU, FKSV)
- UL File Number: E72928 (FKSO, FKSP, FKSU, FKSV)
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 10A @ Ta 40 °C / 250VAC; 50Hz
1 - 10A @ Ta 40 °C / 125VAC; 60Hz
standard < 0.5mA (250V / 60Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7kVDC between L-N
> 2.7kVDC between L/N-PE
Test voltage (2sec)
-25°C to 85°C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Screw: max 8mm
appliance inlet/-outlet
Fuseholder
C14 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10A,
Protection Class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 or 6.3 x 32mm
5 x 20: 2.5W (1 pole)/ 2W (2-pole) per
pole
6.3 x 32: 3.15W (1 pole)/ 2.5W (2-pole)
per pole
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
2-pole, non-illuminated, acc. to IEC
61058-1
Dielectric Strength
Rated Power Acceptance @
Ta 23 °C
Allowable Operation Temp.
Climatic Category
IP-Protection
Protection Class
Power Acceptance @ Ta >
23°C
Terminal
Panel Thickness s
Line Switch
Mounting screw torque max 0.5Nm
Thermoplastic, black, UL 94V-0
Material: Housing
Technical Details
Voltage Selector
Line Filter
optional, step, 2-4 digits
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
MTBF
> 1'200'000h acc. to MIL-HB-217 F
1
EMC Products