C-Series Circuit Breaker – General Specifications  
2
Electrical  
Maximum Voltage  
Mechanical  
Endurance  
AC, 480 WYE/277 VAC, 50/60 Hz  
(see Table A.)  
UL489: AC,240 VAC. (See Table D),  
50/60 Hz, 125 VDC  
Standard current coils: 0.100,  
0.250, 0.500, 0.750, 1.00, 2.50,  
5.00, 7.50, 10.0, 15.0, 25.0, 30.0,  
35.0, 40.0, 50.0, 60.0, 70.0, 80.0,  
90.0 and 100 amps. Other ratings  
available, see Ordering Scheme.  
10,000 ON-OFF operations @ 6 per  
minute; with rated current &  
voltage.  
Trip Free  
All C-Series circuit breakers will trip  
on overload, even when actuator is  
forcibly held in the ON position.  
The operating actuator moves  
positively to the OFF position when  
an overload causes the breaker to  
trip. With mid-trip, handle moves to  
the mid position on electrical trip of  
the circuit breaker. With mid trip  
handle with alarm switch, handle  
moves to the mid position and the  
alarm switch actuates when the  
circuit breaker is electrically  
tripped.  
Current Rating  
Trip Indication  
Standard Voltage Coils DC - 6V, 12V; AC - 120V; other  
ratings available, see Ordering  
Scheme.  
Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux.  
Switch 1.0A, 65 VDC. 0.5A,  
80VDC,1/4 HP, 125VAC,VDE & TUV  
1.0 125 VAC.  
Insulation Resistance  
Dielectric Strength  
Minimum of 100 Megohms at 500  
VDC.  
Physical  
UL, CSA: 1960 V 50/60 Hz for one  
minute between all electrically  
isolated terminals. C-Series Circuit  
Breakers comply with the 8mm  
spacing and 3750V 50/60 Hz  
dielectric requirements from  
hazardous voltage to operator  
accessible surfaces, between  
adjacent poles and from main  
circuits to auxiliary circuits per  
Publications EN 60950 and  
VDE 0805.  
Number of Poles  
1-6 poles ≤ 50A; 1-4 poles @ 51-  
70A; 1-2 poles 71-100A. UL489  
Handle: 1 pole ≤ 100A, 2 pole ≤  
50A; Rocker: 1 pole ≤ 100A.  
Internal Circuit Config. Series (with or without auxiliary  
switch, mid trip & mid trip with  
alarm switch) Shunt & Relay with  
current or voltage trip coils, Dual  
Coil, Switch Only (with or without  
aux. switch). UL489: Series (with or  
without auxiliary switch, mid-trip &  
midtrip with alarm switch).  
Resistance, Impedance Values from Line to Load Terminal -  
based on Series Trip Circuit  
Weight  
Standard Colors  
Approx.112 grams/pole ( 3.95 oz).  
Housing: Black  
RESISTANCE, IMPEDANCE VALUES  
Breaker.  
from Line to Load Terminals  
(Values Based on Series Trip Circuit Breaker)  
Environmental  
1000  
CURRENT  
(AMPS)  
TOLERANCE  
(%)  
Designed and tested in accordance with requirements of  
100  
10  
specification MIL-PRF-55629 & MIL-STD-202 as follows:  
0.10 - 5.0  
5.1 - 20.0  
20.1 - 50.0  
15  
25  
35  
Shock  
Withstands 100 Gs, 6ms sawtooth  
while carrying rated current per  
Method 213, Test Condition “I”.  
Instantaneous and ultrashort curves  
tested @ 90% of rated current.  
Withstands 0.060” excursion from  
10-55 Hz & 10 Gs 55-500 Hz, @  
rated current per Method 204C,  
Test Cond. A. Instantaneous &  
ultrashort curves tested @ 90% of  
rated current.  
Method 106D, i.e., ten 24-hour  
cycles @ +25°C to +65°C,  
80-98% RH.  
Method 101, Condition A (90-95%  
RH @ 5% NaCl Solution, 96 hrs).  
Method 107D, Condition A (five  
cycles @ -55°C to +25°C to +85°C  
to +25°C).  
O
H
M
S
1
0.1  
0.01  
Vibration  
0.001  
0.01  
0.1  
1
10  
100  
AMPERE RATING  
Pulse Tolerance Curves  
60 Hz 1/2 Cycle  
Inrush Pulse Tolerance  
50 Hz 1/2 Cycle  
Moisture Resistance  
Inrush Pulse Tolerance  
I
I
r
r
Time Delay Curves  
Time Delay Curves  
42, 44  
& 46  
22x  
10x  
42, 44  
& 46  
(50 Amps Max.)  
(50 Amps Max.)  
25x  
12x  
Time Delay Curves  
Time Delay Curves  
22, 24 (100 Amps Max.)  
26 (70 Amps Max.)  
22, 24 (100 Amps Max.)  
26 (70 Amps Max.)  
Salt Spray  
t
t
10.0  
20.0  
5.0  
8.33  
16.67  
4.165  
Time in  
Milliseconds  
Thermal Shock  
Operating Temperature -40°C to +85°C  
*Manufacturer reserves the right to change product specification without prior notice.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  

与CA2-B0-14-610-121-D相关器件

型号 品牌 描述 获取价格 数据表
CA2-B0-14-610-612-BG Carling Technologies MAGNETIC CIRCUIT BREAKER,

获取价格

CA2-B0-14-620-321-BG Carling Technologies MAGNETIC CIRCUIT BREAKER,

获取价格

CA2-B0-14-620-3B1-MG Carling Technologies MAGNETIC CIRCUIT BREAKER,

获取价格

CA2-B0-14-650-612-D Carling Technologies MAGNETIC CIRCUIT BREAKER,

获取价格

CA2-B0-16-450-121-BG Carling Technologies MAGNETIC CIRCUIT BREAKER,

获取价格

CA2-B0-16-610-121-BG Carling Technologies MAGNETIC CIRCUIT BREAKER,

获取价格