6
C-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme
C A 3 B 0 10 450 1 2 1 C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
1
2 ACTUATOR
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
2
3 POLES
1
2
One
Two
3
4
Three
Four
5
6
Five
Six
9
660 60.000
9
670 70.000
3
4
4
4,5
4 CIRCUIT
F
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
9
680 80.000
3
A
B
C
D
E
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
G
H
9
685 85.000
9
690 90.000
9
695 95.000
4
4
4,5
9
K
810 100.00
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
CODE AMPERES
A06
6 DC
A32 32 DC
A48 48 DC
A65 65 DC
J12 12 AC
J18 18 AC
J24 24 AC
J48 48 AC
J65
65 AC
5 AUXILIARY / ALARM SWITCH
A12 12 DC
A18 18 DC
A24 24 DC
K20 120 AC
L40 240 AC
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
J06
6 AC
15
8 TERMINAL
10
12
13,15
15
14
11,15
1
2
3
4
5
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
6
Stud M6
11
12
11
11
7
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
6 FREQUENCY & DELAY
9
A
C
3
7
03 DC 50/60Hz, Switch Only
30 DC 50/60Hz Instantaneous
31 DC 50/60Hz Ultra Short
32 DC 50/60Hz Short
10 DC Instantaneous
5/16” Clip Terminal
11 DC Ultra Short
12 DC Short
34 DC 50/60Hz Medium
36 DC 50/60Hz Long
14 DC Medium
16 DC Long
16
9 ACTUATOR COLOR & LEGEND
8
8
8
8
42 50/60Hz Short, High-inrush
Actuator Color
White
I-O
A
C
F
H
K
M
P
ON-OFF
Dual
1
Legend Color
Black
7
20 50/60Hz Instantaneous
44 50/60Hz Medium, High-inrush
B
D
G
J
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
46 50/60Hz Long, High-inrush
Black
2
White
52 DC Short, High-inrush
Red
3
White
8
54 DC Medium, High-inrush
Green
4
White
56 DC Long, High-inrush
Blue
L
5
White
Notes:
Yellow
N
Q
S
U
6
Black
1
Actuator Code:
Gray
7
Black
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles
Orange
Black (short handle)
R
T
8
Black
17
9
White
5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available
with circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip
of the breaker. Available with circuit codes B & C.
Standard multipole units have all poles identical except when specifying auxiliary
switch and/or mixed poles. 4 pole max with VDE. 5th pole available as Series Trip with
Voltage Coil only.
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE
Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D, F, H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100
are available up to two poles maximum.
10 MOUNTING / BARRIERS
MOUNTING STYLE
BARRIERS
VOLTAGE
Threaded Insert
1
6-32 x 0.195 inches
6-32 X 0.195 inches
6-32 X 0.195 inches
ISO M3 x 5mm
no
< 300
< 300
≥ 300
< 300
< 300
≥ 300
2
3
A
C
2
yes
yes
no
18
18
B
D
ISO M3 x 5mm
yes
yes
ISO M3 x 5mm
Front panel Snap-In, 1.00” [25.4mm] wide bezel
4
5
17
E
with Handleguard
no
< 300
11 AGENCY APPROVAL
C
D
E
H
I
UL Recognized, CSAAccepted
VDE Certified, UL Recognized, CSAAccepted
TUV Certified, UL Recognized, CSAAccepted
UL489 Construction: VDE Certified, UL Recognized, CSA Accepted
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
CSAAccepted
UL489 Construction: UL Recognized, CSAAccepted
UL489 Construction: TUV Certified, UL Recognized, CSAAccepted
6
7
8
9
L
R
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
12 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 No marking available. Consult factory. VDE/TUV Approval requires dual
(I-O, ON-OFF) or I-O markings on all handles.
17 Single pole only.
18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or
to be used in applications with a motor.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com