96W Single Output Industrial DIN Rail Power Supply
MDR-100 series
■ Features :
ꢀUniversal AC input / Full range
ꢀProtections: Short circuit / Overload / Over voltage / Over temperature
ꢀZCS/ZVS technology to reduce power dissipation
ꢀCooling by free air convection
ꢀCan be installed on DIN rail TS-35/7.5 or 15
ꢀDC OK relay contact
ꢀNo load power consumption<1W
ꢀLED indicator for power on
ꢀ100% full load burn-in test
ꢀ3 years warranty
..
SPECIFICATION
MODEL
MDR-100-12
MDR-100-24
MDR-100-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
7.5A
4A
2A
0 ~ 7.5A
90W
0 ~ 4A
0 ~ 2A
96W
96W
RIPPLE & NOISE (max.) Note.2 120mVp-p
150mVp-p
200mVp-p
48 ~ 56V
1.0%
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
LINE REGULATION
12 ~ 15V
1.0%
24 ~ 30V
1.0%
1.0%
1.0%
1.0%
1.0%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
Note.5 3000ms, 50ms/230VAC
3000ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC
Note.6 85 ~ 264VAC
47 ~ 63Hz
20ms/115VAC at full load
120 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
PF≧0.95/230VAC
83%
PF≧0.98/115VAC at full load
INPUT
86%
87%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
1.3A/115VAC
0.8A/230VAC
COLD START 30A/115VAC
60A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15.6 ~ 18V 31.2 ~ 36V 57.6 ~ 64.8V
PROTECTION
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, auto-recovery or re-power on to recover
Relay contact rating(max.): 30V/1A resistive
-10 ~ +60℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
OVER TEMPERATURE
DC OK SIGNAL
FUNCTION
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
-40 ~ +85℃, 10 ~ 95% RH
0.03%/℃ (0 ~ 50℃)
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFETY &
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
EMC
(Note 4)
Compliance to EN55011, EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
346K hrs min. MIL-HDBK-217F (25℃)
55*90*100mm (W*H*D)
OTHERS
NOTE
DIMENSION
0.42Kg; 30pcs/13.6Kg/0.82CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Deating maybe needed under low input voltages, please check the derating curve for more detail.
File Name:MDR-100-SPEC 2017-07-07