155W Dual Output with Battery Charger(USP Function)
ADD-155 series
Features :
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage
Battery low/battery polarity protections
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at PFC 67KHz, PWM 134KHz
2 years warranty
SPECIFICATION
MODEL
ADD-155A
ADD-155B
ADD-155C
OUTPUT NUMBER
CH1
CH2
5V
CH3
CH1
CH2
5V
CH3
CH1
CH2
5V
CH3
DC VOLTAGE
13.8V
13.3V
0.5A
27.6V
27.1V
0.5A
54V
53.5V
0.2A
RATED CURRENT
CURRENT RANGE
RATED POWER
9.5A
3A
4.5A
3A
2.3A
3A
0 ~ 10.5A
152.75W
0 ~ 3A
--------
0 ~ 5A
0 ~ 3A
--------
0 ~ 2.5A
149.9W
240mVp-p
CH1: 48 ~ 58V
1.0%
0 ~ 3A
--------
152.75W
200mVp-p
CH1: 24 ~ 29V
1.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
100mVp-p
--------
100mVp-p
--------
100mVp-p
--------
OUTPUT
VOLTAGE ADJ. RANGE
CH1: 12 ~ 14.5V
VOLTAGE TOLERANCE Note.3 2.0%
3.0%
0.5%
2.0%
--------
--------
--------
3.0%
0.5%
2.0%
--------
--------
--------
5.0%
0.5%
2.0%
--------
--------
--------
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1000ms, 90ms/230VAC
2000ms, 90ms/115VAC at full load
20ms/115VAC at full load
124 ~ 370VDC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
24ms/230VAC
88 ~ 264VAC
47 ~ 63Hz
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
PF>0.92 at full load
78%
INPUT
81%
81%
2.5A/115VAC
1.5A/230VAC
COLD START 20A/115VAC
<1mA / 240VAC
40A/230VAC
LEAKAGE CURRENT
OVERLOAD
CH1,CH2:105 ~ 135%
CH3:0.51 ~ 0.9A rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is reoved
CH1:15.87 ~ 18.63V CH1:31.74 ~ 37.26V CH1:62.1 ~ 72.9V
Protection type : Shut down o/p voltage, re-power on to recover
10V 0.8V 19.5V(+1.5V,-1V )
PROTECTION
OVER VOLTAGE
BATTERY LOW
39V 2V
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-20 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
0.03%/ (0 ~ 50 ) on +5V ouput
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
164.2K hrs min. MIL-HDBK-217F (25
199*110*50mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
1Kg; 16pcs/16Kg/0.95CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:ADD-155-SPEC 2008-10-08