MODEL: 61F
Field Network Modules 61-UNIT Series
[4] OPTIONS
blank: none
/Q: With options (specify the specification)
ANALOG I/O MODULE
(Fuji Electric T-Link use)
Functions & Features
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Interfacing analog I/O signals from/to Mini-M or Pico-M
modules with T-LINK
• Saving power and I/O wiring inside an instrumentation
panel
/C02: Polyurethane coating
/C03: Rubber coating
RELATED PRODUCTS
• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)
50
(1.97)
100
(3.94)
GENERAL SPECIFICATIONS
Construction: Plug-in
12
4
5
0
6
9
7
12
4
5
0
6
9
7
Connection
T-Link: Euro type connector terminal (applicable wire
115 (4.53)
mm (inch)
size: 0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: Via Installation Base (model: MxBS2)
Power input: Via Installation Base (model: MxBS2)
Housing material: Flame-resistant resin (black)
Isolation: I/O or T-Link to power
MODEL: 61F-[1][2]-[3][4]
Power indicator: Green LED turns on with power supplied.
ORDERING INFORMATION
• Code number: 61F-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. 61F-161-K/Q)
T-Link SPECIFICATIONS
Configuration: Multi-drop
Communication: Half-duplex
Baud rate: 500 kbps
• Specify the specification for option code /Q
(e.g. /C01)
Transmission media/distance:
KPEV-SB 0.75 mm
2
× 1 pair, 700 m
× 1 pair, 1000 m
T-KPEV-SB, 1.25 mm
2
[1] NO. OF CHANNELS
04: 4 points
Station No.: Rotary switch; 00 - 99
(Factory default setting: 00)
08: 8 points
L RUN indicator: Red LED ON at normal communication
L ERR. indicator: Red LED ON/blinking at communication
abnormality
16: 16 points
[2] I/O TYPE
1: Input
L I/O indicator: Red LED blinking at normal I/O
L COM indicator: RED LED blinking at T-Link normal
communication
2: Output
■ NUMBER OF CONNECTABLE UNITS WITH T-LINK
Up to a maximum of 32 T-LINK devices can be connected in
a single T-LINK system. There is a limit of 100 words in
processor memory. Make sure that the configured word
area to be occupied does not exceed the 100-word range.
(According to the Fuji Electric MICREX-F Users Manual)
It is necessary to consider these criteria when connecting to
this device.
[3] POWER INPUT
AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the UNIT is to be
combined with the M8BS2.)
The below describes the number of words occupied per
device by number of modules.
61F SPECIFICATIONS
ES-6635 Rev.2 Page 1/3