MODEL: 61C
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the 61C is to be
combined with the M8BS2.)
Field Network Modules 61-UNIT Series
ANALOG I/O MODULE
(CC-Link)
[4] OPTIONS
Functions & Features
blank: none
• Interfacing analog I/O signals from/to Mini-M, Pico-M and
other signal conditioner modules with CC-Link
• Saving power and I/O wiring inside an instrumentation
panel
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
50
(1.97)
/C02: Polyurethane coating
/C03: Rubber coating
100
(3.94)
RELATED PRODUCTS
• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)
3 4
2
9
1
0
5
6
7
8
3 4
2
9
1
0
5
6
7
8
3 4
2
9
1
0
5
6
7
8
115
(4.53)
mm (inch)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
MODEL: 61C-[1][2]-[3][4]
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
ORDERING INFORMATION
• Code number: 61C-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. 61C-161-K/Q)
CC-Link: Euro type connector terminal (applicable wire
size: 0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: Via Installation Base (model: MxBS2)
Power input: Via Installation Base (model: MxBS2)
Housing material: Flame-resistant resin (black)
Isolation: I/O to CC-Link to power
• Specify the specification for option code /Q
(e.g. /C01)
Power indicator: Green LED turns on with power supplied.
[1] NO. OF CHANNELS
04: 4 points
CC-Link COMMUNICATION
CC-Link: Conforms to Version 1.10
Station type: Remote device station
Station No. setting: Rotary switch; 1 – 64
Number of occupied stations:
08: 8 points
16: 16 points
[2] I/O TYPE
1: Input
61C-04x: 1 station
2: Output
61C-08x: 2 stations
3: Input/output (Select 16 for no. of channels)
(8 points for input, 8 points for output)
(Use Installation Base model: M8BS2-164)
61C-161: 4 stations
61C-162: 4 stations
61C-163: 2 stations
Remote I/O (RX, RY) is fixed to 32 points.
Baud rate setting: Rotary switch
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps,
10Mbps)
[3] POWER INPUT
AC Power
K: 85 – 132 V AC
Transmission cable: Approved for CC-Link
L RUN indicator: Red LED turns on in an normal condition.
L ERR. indicator: Red LED turns on or flashes in an
abnormality; off with wire breakdown.
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
61C SPECIFICATIONS
ES-6627 Rev.8 Page 1/4
http://www.m-system.co.jp/