Power Entry Modules with Line Filter
5220
https://www.schurter.com /PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole
Screw-on from front side
with 2-pole fuseholder
Snap-in mounting from front side
with 2-pole fuseholder
C14
See below:
Approvals and Compliances
70° C
Description
Characteristics
- Panel mount :
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
Snap-in or screw-on mounting front side
- 3 Functions :
Appliance Inlet Protection class I , Fuseholder for fuse-links 5 x 20 mm
2-pole , Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
For applications according IEC/UL 62368-1 we recommend variants
with bleed resistor
References
Unique Selling Proposition
- Ultra-compact design
- Recessed faston connectors
- High quality filter case made of stainless steel
- Highly resistant since potted filter
Alternative: version without line filter 6220
Alternative: version with V-Lock KFA
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 10A @ Ta 40 °C / 250VAC; 50Hz
1 - 10A @ Ta 40 °C / 250VAC; 60Hz
standard < 0.5mA (250V / 60Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7kVDC between L-N
> 2.7kVDC between L/N-PE
Test voltage (2sec)
-25°C to 85°C
Appliance inlet/-outlet
Fuseholder
C14 acc. to IEC 60320-1,
UL 60320-1, CSA C22.2 no. 60320-1
(for cold conditions) pin-temperature 70
°C, 10A, Protection Class I
2-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20mm
5 x 20: 1.6W (2-pole)
Dielectric Strength
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Allowable Operation Tempe-
rature
Climatic Category
IP-Protection
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
Standard and Medical Version, IEC
60939-2, UL 60939-3, CSA C22.2 no.
8
25/085/21 acc. to IEC 60068-1
front side IP40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8mm
Protection Class
Line Filter
Terminal
Panel Thickness S
Technical Details
> 2'300'000h acc. to MIL-HB-217 F
Mounting screw torque max 0.5Nm
Snap-in: 0.8mm to 3mm
MTBF
Material: Housing
Thermoplastic, black, UL 94V-0
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
1