Power Entry Modules with Line Filter
5200
https://www.schurter.com /PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1-pole
Type 5200, Fuseholder 1-pole with spare com-
Type 5200, Fuseholder 1-pole with spare com-
partment
partment
Screw-On Version
Snap-In Version
C14
Approvals and Compliances
70° C
Description
Characteristics
- Panel Mount :
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
- Suitable for use in equipment according to IEC/UL 60950
Snap-in or screw-on mounting from front side
- 3 Functions :
Appliance Inlet Protection class I , Fuseholder for fuse-links 5 x 20 mm
1-pole , Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
- Variants with V-Lock cord retaining
Unique Selling Proposition
- Ultra-compact design
- Recessed faston connectors
- High quality filter case made of stainless steel
- Highly resistant since potted filter
References
Alternative: version without line filter 6200
Alternative: Standard version
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 10A @ Ta 40 °C / 250VAC; 50Hz
1 - 10A @ Ta 40 °C / 125VAC; 60Hz
standard < 0.5mA (250V / 60Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7kVDC between L-N
> 2.7kVDC between L/N-PE
Test voltage (2sec)
-25°C to 85°C
appliance inlet/-outlet
Fuseholder
C14 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10A,
Protection Class I
1-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
Dielectric Strength
for fuse-links 5 x 20mm
5 x 20: 2W (1 pole)
Rated Power Acceptance @
Ta 23 °C
Allowable Operation Tempe-
rature
Power Acceptance @ Ta >
23°C
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
Climatic Category
IP-Protection
Protection Class
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8mm
Line Filter
MTBF
Terminal
Panel Thickness S
> 2'300'000h acc. to MIL-HB-217 F
Mounting screw torque max 0.5Nm
Snap-in: 0.8mm to 3mm
Material: Housing
Thermoplastic, black, UL 94V-0
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
1
EMC Products