3UA Thermally Delayed Overload Relays
CLASS 10
Technical data according to IEC 947-4
Type
3UA70 11/
3UA70 21
3UA50/
3UA52
3UA55
3UA58
3UA59
3UA60
3UA61/
3UA62
3UA66
3UA68
Trip class
CLASS 10A (2 s <tA ≤10 s at 7.2×Ie from cold state and tA ≤2 min at 1.5×Ie from hot state)
Phase failure sensitivity by
differential phase shift
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
Changeover to automatic
reset
no
RESET button with trip-free
feature
yes
Temperature compensation
Switch position indicator
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
Test button actuates the NO
and NC contacts
Terminal for contactor coil
no1)
yes
yes
no1)
no1)
no1)
no1)
no1)
no1)
Permissible ambient
temperature
°C –25 to +552)
–25 to +55
Degree of protection
Shock resistance
IP 00/open or IP 20 to IEC 947-1 and DIN 40 050
g/ms 8/10
Main circuit
Rated insulation
voltage Ui
AC/DC V 690
690
6
690
6
1000
8
690
6
1000
8
1000
8
1000
8
1000
8
(pollution degree 3)
Rated impulse
withstand voltage Uimp
kV
6
Type of current,
frequency range
DC; AC up to 400 Hz
AC 50 to 400 Hz
Conductor cross-sections
Setting
range
(≤200 A/
>200 A)
Terminal screw
solid or stranded
finely stranded with end
sleeve
M 3
M 4
M 5
M 5
M 5
M 6
M 8
M 8/M 10
185/240
–
M 10
mm2 0.5 to 2.5
mm2 0.5 to 1.5
2.5 to 6
1.5 to 4
1.5 to 25
1 to 16
2.5 to 35
1.5 to 25
1.5 to 25
1 to 16
25 to 70
25 to 50
50 to 120
25 to 95
2×240
–
Flat bars
mm
–
–
–
–
–
–
20×3
20×3/
2×30×5
2×30×5
10 to 14
89 to 124/
14 to 24
124 to 210
Tightening torque
Nm 0.4 to 0.7
lb. in 4 to 6.5
Nm
1 to 1.5
9 to 13
2.5 to 3
22 to 26.5
2.5 to 3
22 to 26.5
2.5 to 3
22 to 26.5
6 to 8
52 to 50
10 to 14
89 to 124
14 to 24
124 to 210
lb. in
Power loss per
conducting path (max.)
at lowest value
W (VA) 0.6
W (VA) 2.3
0.9
1.2
3
2.6
4
0.8
2
5
7
5
7
4 ( 5)
6 ( 9)
at highest value
of the setting range
2.25
10 (12)
15 (22)
1) Not required.
2) The upper setting Io is to be reduced by 0.5% per
1°C excess temperature or a min. space of
5 mm is to be maintained between the units when
several overload relays are series mounted and
simultaneously operated at ambient temperatures
exceeding 25°C.