Thermal-Magnetic Circuit Breakers 3600/3900
Dimensions
Internal connection diagrams
ø11.5
.453
-P10-Si
with shunt terminal (standard)
ø8.5
.335
ø6.5
.256
ø4
and auxiliary contacts (-Si) only 3600
line 1
5
7
line 1
.157
3
3
4
6
>
>
I
I
3 (from IN=8 A)
3 (from IN=8 A)
2
2
1
4 6 3 7 5 2
1
Installation drawing
6.8
.268
6 x 6.8 = 40.8
6 x .268 = 1.61
blade terminals
DIN 46244-A6.3-0.8
(QC .250)
ꢇꢈꢉꢊꢋꢌꢍꢎꢏ ꢋꢊꢉꢋ
ꢐꢊꢉꢍꢎꢑꢇꢊꢒꢉꢓ ꢍꢎꢔꢕꢖꢋꢌꢍꢇꢎꢗ
43
1.69
20
current rating in A
13
.512 .787
50
1.97
Terminal design -P10
1
4
6
ꢀ
ꢁ
ꢂ ꢃ
1
ꢁ
ꢀ
1ꢃꢆꢂ
ꢆ4ꢙꢃ
ꢘꢇꢕꢎꢌꢍꢎꢏ ꢋꢊꢉꢋ
Typical time/current characteristics
3600 0.05…7 A
AC 1)
3600 8…16 A
AC 1)
3900 0.05…10 A
DC 2)
10000
10000
10000
1000
100
1000
100
1000
100
10
1
10
1
10
1
0.1
0.1
0.01
0.1
0.01
0.001
0.01
0.001
0.001
1
1
2
4
6
8 10
20
40 60 80100
2
4
6
8 10
20
40 60 80100
1
2
4
6
8 10
20
40 60 80100
… times rated current
… times rated current
… times rated current
+60 °C
+23 °C
+73.4 °F
-30 °C
-22 °F
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
+140 °F
1) Magnetic tripping currents are increased by 20 % on DC supplies.
2) Magnetic tripping currents are decreased by 20 % on AC supplies.
-22
-30
-4
-20
+14
-10
+32 +73.4 +104 +122 +140
Ambient temp. °F
°C
0
+23
+40
+50
+60
0.76 0.79 0.83 0.88
1
1.08 1.16 1.24
Derating factor
mm
)
This is a metric design and millimeter dimensions take precedence (
inch
2
www.e-t-a.de