Power Entry Modules with Line Filter
DG12
https://www.schurter.com /PG06
IEC Appliance Inlet C14 with Filter, Circuit Breaker TA35 (recessed)
Screw-on with IP67
Screw-on A
Screw-on B
C14
C18
See below:
Approvals and Compliances
70° C
70° C
Description
Characteristics
- Panel mount :
- All single elements are already wired
- Circuit Breaker non-illuminated or illuminated
Screw-on or snap-in mounting from front side
- 3 Functions :
Appliance Inlet protection class I or II , Circuit breaker type TA35 2-pole
, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Suitable for use in medical equipment according to IEC/UL 60601-1
For applications according IEC/UL 62368-1 we recommend variants
with bleed resistor
Other versions on request
- Other rocker marking
- Medical Version (M80)
- Capacitance CX1
- Variants in white
- Filter version with high inductance
Unique Selling Proposition
- IP67 protection
- Recessed rocker switch
- Various mounting options
- V-Lock cord retaining
References
Alternative: version without line filter DG11
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product,
Landing Page
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 10A @ Ta 40 °C / 250VAC; 50Hz
1 - 15A @ Ta 40 °C / 250VAC; 60Hz
standard < 0.5mA (250V / 60Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7kVDC between L-N
> 2.7kVDC between L/N-PE
Test voltage (2sec)
-25°C to 60°C
Appliance inlet/-outlet
Circuit Breakers
C14 C18 acc. to IEC 60320-1
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10A,
Protection Class I or II
Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or non-
illuminated. Optional with undervoltage-
or remote trip release
Short circuit capacity Icn:
2000 A
Standard and Medical Version, IEC
60939, UL 60939-3, CSA C22.2 no. 8
Technical Details
Dielectric Strength
Allowable Operation Tempe-
rature
Climatic Category
IP-Protection
25/060/21 acc. to IEC 60068-1
from front side IP40 or IP65 / IP67 acc.
to IEC 60529
Suitable for appliances with protection
class I or II acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8mm
Line Filter
MTBF
Protection Class
> 100'000h acc. to MIL-HB-217 F
Terminal
Panel Thickness S
Mounting screw torque max 0.5Nm
: S =1.0/1.2/1.5/2.0/2.5/3.0 mm
Thermoplastic, black, UL 94V-0
Material: Housing
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
1
EMC Products